Page 26 - DIN Disconnectors
P. 26
26 EASYLINE XLP FUSE SWITCH DISCONNECTOR 1-2-3- 4 POLES
—
Technical data
—
XLPD0 3-pole
Fuse links XLPD0-FS-E18-3P XLPD0-FB-E18/27-3P XLPD0-FB-E18/36-3P XLPD0-FB-E27/42-3P XLPD0-FB-E33/57-3P XLPD0-FS-1038-3P 2)
Fuse size D01 1) , D02 D02 D02 DII DIII NFC 10x38
Rated operational
voltage Ue AC (V) 400 400 400 500 500 500 690
Rated operational
voltage Ue DC (V) 250 250 500 500
Rated operational
current Ie AC (A) 63 63 63 25 63 32
Utilization category AC22B AC21B
Rated insulation
voltage Ui (V) 500 800
Rated impulse
withstand voltage
Uimp (kV) 6 6 6 6 6 6
Rated conditional
short circuit current (kArms) 50 50 (AC) / 8 (DC) 50 (AC) / 8 (DC) 50 (AC) / 8 (DC) 50 (AC) / 8 (DC) 100
Rated frequency (Hz) 50 50 50 50 50 50
Power loss (Ith)
without fuselink (W) 7 5,9 5,9 1,2 10 1
Max allowed
poweloss in the
Fuse per phase (W) 5,5 5,5 5,5 4 7 3
1) Together with D02 reducer part 2CDE000011R190 also suitable for fuse links D01
2) UL -ratings Operational current 30A and Operational voltage 600V (AC/DC) at 50kA