26               EASYLINE XLP FUSE SWITCH DISCONNECTOR 1-2-3- 4 POLES



          —

          Technical data











          —
          XLPD0 3-pole
          Fuse links           XLPD0-FS-E18-3P  XLPD0-FB-E18/27-3P   XLPD0-FB-E18/36-3P  XLPD0-FB-E27/42-3P  XLPD0-FB-E33/57-3P  XLPD0-FS-1038-3P  2)
          Fuse size              D01  1) , D02   D02          D02           DII           DIII       NFC 10x38
          Rated operational
          voltage Ue AC  (V)       400           400          400           500           500       500    690
          Rated operational
          voltage Ue DC  (V)                     250          250           500           500
          Rated operational
          current Ie AC  (A)        63           63            63           25            63            32
          Utilization category    AC22B                                                               AC21B
          Rated insulation
          voltage Ui    (V)        500                                                                 800
          Rated impulse
          withstand voltage
          Uimp          (kV)        6             6            6             6            6             6
          Rated conditional
          short circuit current  (kArms)  50  50 (AC) / 8 (DC)  50 (AC) / 8 (DC)  50 (AC) / 8 (DC)  50 (AC) / 8 (DC)  100
          Rated frequency  (Hz)     50           50            50           50            50            50
          Power loss (Ith)
          without fuselink  (W)     7            5,9           5,9          1,2           10            1
          Max allowed
          poweloss in the
          Fuse per phase  (W)      5,5           5,5           5,5           4            7             3

          1)  Together with D02 reducer part 2CDE000011R190 also suitable for fuse links D01
          2)  UL -ratings Operational current 30A and Operational voltage 600V (AC/DC) at 50kA