            External lightning protection                                                                                          Coping with direct lightning strikes

                                                                                                                                   Conventional and isolated lightning protection





                                                                                                                                   Lightning protection is protection against fire and, above all, personal injury. Lightning
                                                                                                                                   protection systems form a protective sheath around the building by intercepting direct
                        A                                                                    A                                     lightning strikes and discharging them to the ground.
                                                                   C


                                                                                                                                   External lightning protection is set out in the IEC 62305 standard and protects buildings from the effects of a direct lightning
                                                                                                                                   strike. A complete lightning protection system consists of the following elements: air-termination system, down conductor
                                                                                                                                   system, earth-termination system, lightning equipotential bonding or separation distances.

                                                                                                            B                      The lightning current flows into the down conductors via the air-termination system and is conducted to the ground in a
                                                                                                                                   controlled manner. The important thing here is that the separation distances from conductive metal parts are maintained.
                                                                                                                                   Otherwise, dangerous flashover can occur which may cause sparking and start a fire. Lightning equipotential bonding reduces
                                                                                                                                   the potential differences caused by the lightning current. This is achieved by connecting all isolated conductive system parts
                                                                                                                                   directly by means of conductors or by means of surge protective devices (SPDs).
                                                                                                                                   There are two types of external lightning protection system for a building:

                                                                                                                                   Conventional lightning protection system

                                                                                                                                   If the separation distances from metal and/or earthed installations is maintained con-
                                                                                                                                   sistently, the air-termination and down-conductor systems – for example round wires
                                                                                                                                   or air-termination rods – can be installed on the surface of the building.
                                                                                                                                   Please note: Special requirements must be observed for buildings with thatched roofs!

                                                                                                                                     Product examples for conventional lightning protection can be found on page 8.
                                                                                                                                   If separation distances cannot be maintained due to the properties of the building,
                                                                                                                                   consistent lightning equipotential bonding is required. As an alternative, an isolated
                                                                                                                                   lightning protection system can be installed.
            External lightning protection


             A   Air-termination system                                         Product examples    Part No.
                                                                                                                                   Isolated lightning protection
                                              Correctly dimensioned air-termination   Self-supporting air-   105 530
                                              systems prevent direct lightning strikes to a   termination rod
                                              building. They consist of rods, spanned wires /  Roof conductor holder  253 050      In case of an isolated lightning protection system, air-termination rods, air-termination masts or masts spanned with cables
                                              cables and intermeshed conductors and can   Air-termination rod  103 220             protect the entire building against the effects of a direct lightning strike. The separation distance s between the lightning
                                              be combined as needed.            DEHNiso spacer      106 115                        protection system, the building and installations as pipes, chimnies, coolers, wires and antennas etc. must be maintained.

                                                                                                                                   HVI Lightning Protection
                                                                                                                                   HVI Lightning Protection comprises a high-voltage-resistant insulated down conductor
             B   Down conductor                                                 Product examples    Part No.                       which, in combination with the relevant supporting tubes and air-terminations rods,
                                              A down conductor is a conductive connection   DEHNalu wire  840 028                  forms the isolated lightning protection system. The special feature is that the lightning
                                              between the air-termination system and the   Screw, plastic base    207 109          current carrying conductor is wrapped in semi-conductive insulating material so that
                                              earth-termination system. It discharges the   and dowel                              the necessary separation distance – be it from other conductive parts of the building
                                              intercepted lightning current to the earth-   Round wire  860 115                    or electrical lines and pipes – can be easily maintained. Consequently, further meas-
                                              termination system without damaging the   Number plate  490 110                      ures such as the additional connection of a braided shielded are not required.
                                              building, e.g. as a result of excessive heat.
                                                                                                                                   HVI Conductors also cater to the desire for a modern appearance and design. The
             C   Connection components (clamps)                                 Product examples    Part No.                       conductors  can  be  painted  to match the  colour  of  the  building  or even installed
                                              Clamps interconnect conductors or connect   MV clamp  390 051                        behind the façade. The system can thus be optimally adapted to the architecture of a
                                              them to the installation. They must be subjec-  UNI disconnecting clamp,   459 129   building and offers entirely new design possibilities.
                                              ted to a lightning current test according to    stainless steel
                                              IEC 62561-1. DEHN components fully meet   Saddle clamp,    365 031                   Glass-fibre reinforced plastic (GRP)
                                              this requirement and are reliably tested.  aluminium
                                                                                Downpipe clamp      423 019                        As an alternative, air-termination and down-conductor systems made of electrically insulating material such as GRP can be
                                                                                                                                   mounted on the object to be protected.