Page 10 - Enclosed
P. 10

10               SAFETY SWITCHES AND ENCLOSED SWITCH-DISCONNECTORS SAFE AND DEPENDABLE PERFORMANCE




         —
         Technical data
         Safety switches







          —
          Safety switches type OT_
          Data according to IEC 60947-3  Switch size  16  25    36      63     75      90     90     125     160
          Plastic enclosed    Switch type    OTP/OTE  OTP/OTE  OTP/OTE  OTP  OTP/OTE  OTP/OTE  OT_G  OT_G    OT
          Steel sheet enclosed                  OTL     OTL    OTL     OTL    OTL     OTL                    OT
          Stainless steel sheet enclosed        OTR    OTR     OTR     OTR    OTR     OTR                  OT_EV_
          Rated Insulation voltage        V     750     750    750     750     750    750    1000    1000   1000
          Rated thermal current   40ºC    A      40     63      80     115     115    125     90     125     160
                                  60ºC    A      32     50      63      80     80     100     90     125     160
          Rated operational power, AC-23A  230V     kW/A  5.5/23  7.5/30  11/45  18.5/63  22/80  22/90  22/90  37/125  48/160
                                  400V    kW/A  7.5/16  15/30  22/45  30/63  37/80   45/90  45/90  55/125  80/160
                                  500V    kW/A  7.5/16  15/30  22/45  30/50  37/60   45/70  55/90  75/125  112/160
                                  690V    kW/A  7.5/10  15/20  15/20  30/35  37/40   45/50  75/90  110/125  144/160
          Rated conditional short-  50kA,   kA  6.5     13      13     16.5   16.5    16.5    24      24      24
          circuit current        400V 1)
          r.m.s and corresponding   Fuse size:  gG/aM  40/32  100/80  100/80  125/125  125/125  125/125  200/200  200/250  355/315
          cut-off current     50kA, 690V 1)  kA  4      11      11      10     10      10     24      24      35
          of the fuse in single-phase test
          according to IEC60269
                                Fuse size:  gG/aM  25/16  80/63  80/63  63/63  63/63  63/63  200/200  200/200  355/315
          Used switch type                     OT40_  OT63_   OT63_  OT100_  OT100_  OT125F_  OT160G_  OT160G_  OT160EV_
          Cable size                    mm²  0.75…10  1.5…35  1.5…35  10…70  10…70  10…70   10…70   10…70
          Terminal bolt size            mm                                                                 M8x25






          Data according to IEC 60947-3  Switch size  200  250    315      400     630      800     1000    1250
          Plastic enclosed    Switch type         OT      OT       OT      OT       OT      OT       OT      OT
          Steel sheet enclosed                    OT      OT       OT      OT       OT      OT       OT      OT
          Stainless steel sheet enclosed          OT      OT       OT      OT       OT      OT       OT      OT
          Rated Insulation voltage        V     1000     1000    1000     1000     1000    1000     1000    1000
          Rated thermal current   40ºC    A      200      250     315      400     570      720     1000    1250
                                  60ºC    A      200      200     315      320     460      580
          Rated operational power, AC-23A  230V     kW/A  55/200  75/250  90/315  110/400  180/570  200/720  315/1000  400/1250
                                  400V    kW/A  110/200  132/250  160/315  220/400  315/570  400/720  560/1000  710/1250
                                  500V    kW/A  132/200  160/250  200/315  280/400  400/570  500/720  710/1000  900/1250
                                  690V    kW/A  160/200  200/250  250/315  355/400  560/570  710/720  1000/1000  1200/1250
          Rated conditional short-  50kA,   kA    35      35      50.5    50.5     71.5     71.5     75
          circuit current        400V 1)
          r.m.s and corresponding   Fuse size:  gG/aM  355/315  355/315  500/500  500/500  800/1000  800/1000  1000/1000
          cut-off current
          of the fuse in single-phase test   50kA,   kA  35  35   50.5    50.5     71.5     71.5     75
                                    1)
          according to IEC60269  690V
                                Fuse size:  gG/aM  355/315  355/315  500/500  500/500  800/1000  800/1000  1000/1000
          Used switch type                     OT200_  OT250_   OT315_   OT400_  OT630_   OT800_  OT1000_  OT1250_
          Cable size                    mm²
          Terminal bolt size            mm     M8x25    M8x25   M10x30  M10x30   M12x40   M12x40  M12x50   M12x50
   5   6   7   8   9   10   11   12   13   14   15