SAFET Y SWITCHES                                                                   11




          —
          Technical data
          Safety switches

                                                                                                                      02





          —
          Aluminium enclosed safety switches
          Data according to IEC 60947-3  Switch type          OTA16_X  OTA25_X  OTA40_X  OTA63_X  OTA80_X  OTA100_X  OTA125_X
          Rated insulation voltage and rated   Pollution degree 3  50 Hz   V  750   750   750   750  750   750   750
          operational voltage AC20/DC20             1 min.
          Rated thermal current        Ambient 40 °C  2)   A      25     32     40      63     80     115    125
                                        Ambient 60 °C      A     20      25     32      50     63     80     100
          Rated operational current,  AC-23A     up to 415 V  A   16     20     23      63     75     80      90
                                                    500 V  A      16     20     23      45     58     60      70
                                                    690 V  A      10     11      12     20     20     40      50
          Rated operational power, AC-23A        220...240 V  kW  3       4     5.5     11     22      22     22
          (These values are given for guidance and   400...415 V  kW  7.5   9    11     22     37      37     45
          may vary acc. to the motor manufacturer)
                                                 440...500 V  kW  7.5     9      11     22     37      37     45
                                                    690 V  kW    7.5      9      11     15    18.5     37     45
          Rated conditional short-circuit current Iq   Iq 50kA, 415V   Îc   kA  6.5   6.5   6.5   13   13   16.5   16.5
          (r.m.s.) and corresponding max. Allowed   Max. OFA_fuse size
          cut-off current Îc of fuse. The cut-off   gG/aM  A/A  40/32  40/32  40/32  100/80  100/80  125/125  125/125
          current Îc referes to values listed by fuse
          manufacturers (single phase test acc. To   Iq 100kA, 500V   Îc  kA  –  –  –   17     17      –       –
          IEC60269)                   Max. OFA_fuse size
                                                   gG/aM  A/A     –       –      –   100/80  100/80    –       –
                                         Iq 10kA, 690V   Îc  kA   –       –      –      –       –     8.2     8.2
                                      Max. OFA_fuse size
                                                   gG/aM  A/A     –       –      –      –       –   125/100  125/100
                                         Iq 50kA, 690V   Îc   kA  4       4      4      11     11      10     10
                                      Max. OFA_fuse size
                                                   gG/aM  A/A   25/16  25/16   25/16  80/63  80/63   63/63  63/63
          Rated short-time withstand current  r.m.s. -value  Icw  690 V, 1 s   kA  0.5  0.5  0.5   1   1.5   2.5   2.5

          Cable size                 Cu-wire size suitable   mm²  0.75...10  0.75...10   0.75...10   1.5...35   1.5...35   10...70   10...70
                                     for terminal clamps