12               SAFETY SWITCHES AND ENCLOSED SWITCH-DISCONNECTORS SAFE AND DEPENDABLE PERFORMANCE




          —
          Technical data
          Safety switches







         —
         Technical data according to IEC 60947-3
         Type / size                                  OTA 16_  OTA 25_  OTA 40_  OTA 63_ LBAS _45_  LBAS _75_ LBAS _90_
         Rated insulation voltage                 V      750      750     750      750     750      750      750
         Rated thermal current and rated   40ºC   A       25       32      40       63      63       80      125
         operational current AC20/DC20    60ºC    A       20       26      32       50      50       64     100
         Rated operational power and   up to 415V  kW/A  7.5/16  15/30   22/45   30/63    25/63    37/75   45/90
         current,                     up to 500V  kW/A  7.5/16  15/30    22/45   30/45    22/45   37/58    45/70
         AC-23A
                                          690V  kW/A   7.5/10   15/20    15/20  18.5/20   15/20  18.5/20   45/50
         Rated conditional short-circuit  50kA, 415V  kA  6.5      13      13       13      13       13     16.5
         current r.m.s and corresponding  Fuse size:   A  40/32  100/80  100/80  100/80  100/80  100/80  125/100
         cut-off current of the fuse in single-  gG/aM
         phase
         test according to IEC60269  50kA, 690V  kA      6.5       13      13       13      13       13     16,5
                                       Fuse size:   A   25/16   80/63    80/63   80/63    80/63   80/63  125/100
                                         gG/aM
         Rated frequency                         Hz    50/60    50/60    50/60   50/60    50/60   50/60    50/60
         Cu-wire size suitable for terminal.    mm 2  0.75...10  1.5…35  1.5…35  1.5…35  1.5…35  1.5…35   10…70
         Terminal bolt size
         Used switch type                             OT40F3   OT63F3  OT63F3   OT80F3   OT63F3  OT80F3  OT125F3




         Type / size                           OTA 125_  OTA 160_  OTA 200_  OTA 250_  OTA 315_  OTA 400_  OTA 600_
         Rated insulation voltage          V      1000      1000     1000     1000     1000      1000       1000
         Rated thermal current and   40ºC  A       160       160      200      250      315      400        600
         rated operational current   60ºC  A       160       160      200      250      315       320       480
         AC20/DC20
         Rated operational power   up to 415V kW/A  55/125  75/135  110/200  132/250  160/315  220/440   315/540
         and current,           up to 500V kW/A  55/90    75/135  132/200   160/250  200/315  280/400    400/552
         AC-23A                     690V kW/A     55/70    75/80  160/200   200/250  250/315  355/400    560/551
         Rated conditional short-  100kA, 500V  kA  40.5    40.5     61.5      61.5     61.5     61.5        90
         circuit                 Fuse size:   A  315A/315A  315A/315A 500A/500A  500A/450A 500A/450A  500A/450A  800A/1000A
         current r.m.s and         gG/aM
         corresponding         80kA, 690V  kA      40.5     40.5     61.5      61.5     61.5     61.5        90
         cut-off current of the fuse in
         single-phase            Fuse size:   A  315A/315A  355A/315A 500A/500A 500A/500A 500A/500A 500A/500A  800A/1000A
         test according to IEC60269  gG/aM
         Rated frequency                   Hz    50/60     50/60    50/60    50/60     50/60    50/60      50/60
         Cu-wire size suitable for       mm 2        8        8        10       10       10        10         12
         terminal.
         Terminal bolt size
         Used switch type                     OT160EV12  OT160EV12  OT315E03  OT315E03  OT315E03  OT400E03  OT630E03
   7   8   9   10   11   12   13   14   15   16   17