Semiconductor fuses
                                                   Semiconductor (AC) fuses


                                                                 Protistor Square-body Fuses
                                                                                ®
                                                                         PSC gR/aR sizes 000/00
                                                        gR/aR - 500 to 690 VAC DIN 000






                                                                                      GERMAN STANDARD
                                                                            gRB - URB from 20 to 400 A

                                                                                                      Size: 000
             - EXTREMELY HIGH BREAKING CAPACITY FUSES: PROTECTION OF
              POWER SEMICONDUCTORS ACCORDING TO IEC 60269-1 and 4

             - 690V VOLTAGE RATING (RATING 20 TO 400 A)
             - gR CLASS (gRB RATINGS 20 TO 125 A) ACCORDING TO VDE 636-23
             - CLEARING ALL OVERLOADS
             - IMPROVING SAFETY AND PROTECTION
             - ENABLING SELECTIVE COORDINATION WITH ALL FUSES

             - aR CLASS (URB RATINGS 80 TO 400 A) ACCORDING TO VDE 636-23
              AND IEC 60269.4


             - ALL MODELS COMPLYING WITH DIN 43653-00C ARE
              WITH OR WITHOUT BLOWN FUSE INDICATION
              WITH TRIP INDICATOR


             - MODEL COMPLYING WITH DIN 43620 (00C) STANDARD WITH
              BLOWN FUSE INDICATION - WITH TRIP INDICATOR




             Main Characteristics


              Voltage           Current  Pre-arcing Total clearing
              rating   Class    rating   I t @ 1 ms  I t @ 660V     Watts loss          Tested         Estimated
                                                    2
                                          2
             U ( VAC)           IN (A)    I tp (A s)  I tt (A s)  0.8 IN            IN  Breaking Capacity  Breaking Capacity
                                                     2
                                               2
                                          2
                                                         2
              N
                                  16        8,2        60         -         5,6
                                  20        12         80        3.8        7
                                  25        20        150        5.0        9
                                  32        39        270        5.5        10
               690     gRB        40        70        460        6.6        12         200 k A          300 k A
                                  50        102       730        7.7        14         @ 690 V          @ 690 V
                                  63        210      1500        8.8        16
                                  80        475      2900        9.9        18
                                 100        970      6000        11         20
                                 125       1900      11800       11.6       21
                                  80        390      2500        11.6       21
                                 100        690      4200        12.7       23
                                 125       1300      8900        14.3       26         200 k A          300 k A
               690     URB       160       2700      16000       17.0       31         @ 690 V          @ 690 V
                                 200       5250      31500       19.8       36
                                 250       9900      52000       24.8       45
                                 315       15500     82000       31.9       58
                                 350       22400    110000*      31.9       58         120 k A
               500     URB
                                 400       33200    160000*      36.3       66         @ 500 V
             * @ U n
             Minimum operating voltage for blown fuse indicator: 20 V
             Minimum operating voltage for trip-indicator: 20 V
                                                          SCAC50                                               12/04