Semiconductor fuses
       Semiconductor (AC) fuses


       Protistor Square-body Fuses
                     ®
       PSC aR sizes 3x - 450V to 700 VAC
       Curves set






       Size 30
                                                                 Cut-off characteristics

                                                               Below, right: Curves indicating for each rated-
                                                               current the peak value I that the current may
                                                                                     c
                                                               reach as a function of the prospective fault
                                                      3,2 mm
                                                               current Ip.



































                                                           Time-current characteristics
                 Size
                                                         Above, left: Curves indicating pre-arcing time for
                 30
                                                         each rated current as a function of RMS value of
                                                         pre-arcing current I.
                                                         - Tolerances on this current ± 8 %.
                                                         - Beyond 30 sec or 10 sec, small overloads must be
                                                         eliminated by another device.
                                                         - Curve CC’ represents the maximum times taken by
                                                         the associated device to clear small overloads; only
                                                         its horizontal line is represented. Its oblique line must
                                                         be plotted according to sketch, top right corner.
                                                         - The intersection of the fuse and CC’ curves indicates
                                                         the minimum breaking current Ipm of the fuse.



                                                           Maximum values of total
                                                         operating I t and total operating
                                                                         2
                                                         times
                                                         Left: Horizontal curves indicating the maximum
                                                                                   2  2
                                                         values of total operating I t (I t ) as function of the
                                                                                       t
                                                         prospective current I at 660 V, cos ϕ = 0.15.
                                                                              p
                                                         The oblique lines indicate the corresponding total
                                                         operating time T , with pre-arcing time in brackets.
                                                                          t