Page 237 - Ferraz semiconductor DIN
P. 237

Semiconductor fuses
                                                   Semiconductor (AC) fuses


                                                                 Protistor Square-body Fuses
                                                                                ®
                                                      PSC aR sizes 3x - 450V to 700 VAC
                                                                                                 Curves set






                                                                                                         Size 31



                                                                       Cut-off characteristics
                                                                     Below, right: Curves indicating for each rated
                                                                     current the peak value I that the current may
                                                                                            c
                                                                     reach as a function of the prospective fault
                                                                     current I .
                                                                             p
































                     Size                                        Time-current characteristics
                      31
                                                               Above, left: Curves indicating pre-arcing time for
                                                               each rated current as a function of RMS value of pre-
                                                               arcing current I.
                                                               - Tolerances on this current ± 8 %.
                                                               - Beyond 30 sec or 10 sec, small overloads must be
                                                               eliminated by another device.
                                                               - Curve CC’ represents the maximum times taken by
                                                               the associated device to clear small overloads; only its
                                                               horizontal line is represented. Its oblique line must be
                                                               plotted according to sketch, top right corner.
                                                               - The intersection of the fuse and CC’ curves
                                                               indicates the minimum breaking current Ipm of the
                                                               fuse.


                                                                 Maximum values of total
                                                                              2
                                                               operating I t and total operating
                                                               times
                                                               Left:  Horizontal curves indicating the maximum
                                                               values of total operating I t (I t ) as function of the
                                                                                          2
                                                                                       2
                                                                                            t
                                                               prospective current I at 660 V, cos ϕ = 0.15.
                                                                                  p
                                                               The oblique lines indicate the corresponding total
                                                               operating time T , with pre-arcing time in brackets.
                                                                               t
                                                          SCAC86                                               12/04