Page 326 - Ferraz semiconductor DIN
P. 326

Semiconductor fuses
                                                   Semiconductor (AC) fuses


                                                                            Other Protistor Fuses
                                                                                                      ®
                                                                                           Ferrule Fuses
                                                22x58 gRC (URD) - 600 V to 690 VAC






             EXTREMELY BREAKING CAPACITY RATING FUSES: PROTECTION OF SEMICON-
             DUCTORS
             IN COMPLIANCE WITH IEC STANDARD 60269.1 AND 4
             600 - 690 V VOLTAGE RATING (CURRENT RATING 12 TO 135 A)
             AS PER IEC 33
             gR CLASS (CURRENT RATING 12 TO 100 A) ACCORDING TO VDE 636-23
             - CLEARING ALL OVERLOADS
             - IMPROVED SAFETY AND PROTECTION
             - ENABLING SELECTIVE COORDINATION AMONG ALL
              DISTRIBUTION CIRCUIT FUSES
             aR CLASS (CURRENT RATING 125 AND 135 A) AS PER VDE 636-23 AND IEC
             60269.4
             TWO MODELS COMPLYING WITH NF C 63210 AND 63211
             WITH OR WITHOUT TRIP-INDICATOR

             gRC FUSES ARE 700VAC-DC UL RECOGNIZED







             Main Characteristics


              Voltage           Current   Pre-arcing  Total
              rating   Class     rating   I 2 t @ 1 ms  clearing  Watts loss           Tested         Estimated
              U ( V )           I ( A )   I 2 tp (A 2 s)  I 2 t @ U N             Breaking capacity  Breaking capacity
                                 N
               N
                                                    I 2 tt (A 2 s)  0.8 I N  I N
                                  20         17       125       4.0       6.5         100k A
                                  25         39       280       4.5       7.5         @ 690 V
                                  32         72       490       5.0       9.0                          300k A
                                  40        118       785       5.5        10                          @ 690 V
                                  50        242      1390       7.0       11.5
               690      gRC
                                  63        430      2460       8.0       13.5
                                  80        970      5565       9.0       15.5
                                 100        2080     11950      10         17
                                 125        2900     14000      14         22         100k A           300k A
               600     URD       135        3360     17700      15         25         @ 600 V          @ 600 V




             Minimum operating voltage for the trip-indicator: 20 V
             See Fuse Blocks and Fuse Holders section

















                                                          SCAC178                                              12/04
   321   322   323   324   325   326   327   328   329   330   331