Page 8 - Ferraz semiconductor DIN
P. 8

Semiconductor fuses
       Semiconductor (AC) fuses


                     ®
       Protistor Square-body Fuses
       PSC gR/aR sizes 000/00
       gR/aR - 600 to 690 VAC DIN 00






       gRB-URB from 16 to 450 A
       Size: 00



       EXTREMELY HIGH BREAKING CAPACITY FUSES:
       PROTECTION OF POWER SEMICONDUCTORS
       AS PER IEC STANDARD 60269.1 AND 4

       690 V VOLTAGE RATING

       gR CLASS (gRB RATINGS 16 to 160 A) AS PER VDE 636-23
       - CLEARING ALL OVERLOADS
       - IMPROVING SAFETY AND PROTECTION
       - ENABLING SELECTIVE COORDINATION WITH ALL FUSES

       aR CLASS (URB RATINGS 16 TO 450 A) ACCORDING TO
       VDE 636-23 AND IEC 60269-4

       CONNECTIONS ACCORDING TO
       - DIN 43653/00 80 AND 110 mm BETWEEN AXES
       - DIN 43620/00 SOLID BLADES
       WITH AN INDICATING PAWL ACTIVATING A MICROSWITCH IF NEEDED

       Main Characteristics



        Voltage          Current  Pre-arcing  Total clearing  Watts loss        Tested           Estimated
        rating   Class    rating  I t @ 1 ms  I t total@  0.8 IN          IN  Breaking Capacity  Breaking Capacity
                                              2
                                   2
                                               2
        U (V)             I (A)    I tp (A 2s)  UN I tt (A 2s)
                                   2
                          N
          N
                           16         8         61       2.7      5
                           20        12         86       3.3      6
                           25        18        140       4.4      8
                           32        39        250       6.0      11           200 k A            300 k A
                           40        68        450       7.1      13           @ 690 V            @ 690 V
                  gRB      50        116       750       8.8      16
                           63        210       1400      9.9      18
                           80        525       3000      10.5     19
                           100       970       5400      10.7    19.5
                           125      1710       9600      13.2     24
         690
                           160      4270      22400      13.7     25
                           16         7         52       3.8      7
                           20        10         75       5.0      9
                           25        15        120       6.0      11
                           32        32        210       8.2      15
                           40        61        400       9.9      18
                           50        102       700       11.5     21
                 URB       63        177       1200      12.6     23           200 k A            300 k A
                           80        390       2200      13.8     25           @ 690 V            @ 690 V
                           100       692       3900      15.4     28
                           125      1170       6600      18.1     33
                           160      2680      14 000     19.8     36
                           200      4690      24 000     23.1     42
                           250      8300      42 500     27.5     50
                           315      17 520    81 000     31.9     58
                          350 •     25 450    118 000    33.0     60
                          400 •     33 200    150 000    38.5     70
         600     URB      450 **    51 850    196 000    40.7     74        200 k A @ 600 V    300 k A @ 600 V
       NOTE: voltage rating of 350-400-450 A rated fuses is defined with a CC’ curve at 1 second limited by minimum breaking current.
       • Voltage rating: 690 V with CC’ at 1s  -   450 V with CC’ at 10 s
       ** Voltage rating: 600 V with CC’ at 1s  -   450 V with CC’ at 10 s
       Minimum operating voltage for trip indicator = 20 V


                                                          SCAC55
       12/04
   3   4   5   6   7   8   9   10   11   12   13