Semiconductor (A) fuses
       Semiconductor (AC) fuses


       American Round Fuses

       Form 101 Range
       A50QS






       Semiconductor Protection Fuses

       I t Data – 500 Volts AC
        2
                                 2
                                 I t data
               Melting
        Fuse             Max Clearing I t @ 500 VAC
                                    2
                 I t
                  2
       Ampere
                2
                     3
              (A s X 10 ) 1 fuse (fig A)  2 Fuses in series
        Rating
                                         3
                                    2
                              3
                         2
                       (A s X 10 )  (A s X 10 )(fig B)  500 VAC  Fault    Load     500 VAC      Fault    Load
          35     .09      .56          .34
          40     .11      .69           .4
                                                             Fig. A                        Fig. B
          50     .18      1.1          .68
          60     .25      1.6          .94
          70     .31      1.9          1.1
                                                                        2
          80     .43      2.6          1.5                  Clearing I t vs. AC Operating Voltage
          90     .57      3.6          2.1
         100     .74      4.4          2.7
         125     .94      5.6          3.4
         150     1.5       9           5.4
         175     2.5      15            9
         200     3.3      20           12
         225     4.1      25           15
         250     4.9      29           18
         300     9.2      55           33                      CORRECTION FACTOR FOR I 2 T
         350     15       88           53
         400     16       98           59
         450     21       130          76
         500     26       160          94
         600     37       220          130
         700     53       270          160
         800     72       360          220
         900     98       500          300
         1000    112      560          330
         1200    200      930          550                             OPERATING VOLTAGE (AC RMS VOLTS)
                     2
       Clearing I t at 500V DC,                         DC Voltage Capability vs. Time Constant
       100kA, L/R = 10 ms


                                              2
         Ampere   Clearing I t  Ampere  Clearing I t
                         2
                    2
                         3
         Rating   (A s X 10 )  Rating  (A s X 10 )
                                              3
                                         2
           35        .48       250        25
           40        .58       300        47
           50        1.0       350        75
           60        1.3       400        83
           70        1.6       450        110
           80        2.2       500        130          DC VOLTAGE CAPABILITY
           90        3.0       600        190
          100        3.8       700        220
          125        4.8       800        260
          150        7.7       900        350
          175        13        1000       430
          200        17        1200       660
       DC Application:  A50QS Fuses have been designed for
       both AC and DC operation. A50QS fuses (70-600) have
       UL Component Recognition at 500V DC and have been
       tested to circuit parameters as defined in Standard 198L.
                                                                           L/R TIME CONSTANT (MS)


                                                          SCAC15
       12/04
   10   11   12   13   14   15   16   17   18   19   20