130              GENER AL PURPOSE ENCLOSURES HE AV Y DUT Y AND INDUSTRIAL ENCLOSURES




          —
          Accessories
          Thermostat




                                    Function
                                    FZK 011, ZR 011 and ETR 011 elements regulate and control the temperature inside the enclo-
                                    sure by controlling the small heaters, fans, heat exchangers and cooling units.

                                    FZK 011
                                    Mechanical thermostat used for controlling heating resistors, air conditioning units, filter
                                    fans or signaling. It obtains ambient temperature readings and can switch resistive and in-
                                    ductive loads thanks to its snap switching.
          FZK 011
                                    ZR 011
                                    Two thermostats in one unit:
                                    •   thermostat (contact normally closed) for heating resistor regulation.;
                                    •   thermostat (contact normally open) for regulating filter fans, heat exchangers and air con-
                                     ditioning units or for triggering signals when the temperature threshold is exceeded.
                                    Unlike a thermostat with inverter switch, the dual thermostat allows the heating resistor and
                                    air conditioning unit to be connected independently at different temperature ranges.

                                    ETR 011
          ZR 011
                                    The mechanical thermostat is used for controlling heating resistors, air conditioning units,
                                    filter fans or signaling. The thermostat obtains ambient temperature readings and can
                                    switch resistive and inductive loads thanks to its inverter switch (relay). The LED integral to
                                    the adjustment button lights up when the contact is closed (when the heating resistor is in
                                    operation, for example).

                                    Technical specifications
                                    Type                 FZK 011           ZR 011             ETR 011
                                    Adjustment range:    +5 to +60°C or -20 - +35°C  0 to 60°C    +20 °C
                                    hysteresis temperature  0.5 K          7 K                4 K (±1 K tolerance)
          ETR 011
                                    Contact type         switching contact: single- NC        NO
                                                         pole
          Connection diagram        Power                NC 10 A (4) 250 V AC   10 A (2) 250 V AC   AC 240 V, 8 (1.6) A
                                                         NO 5 A (2) 250 V AC   Resistive load  AC 120 V, 8 (1.6)
                                                         Resistive load                       DC 100 W to DC 24 V
           FZK 011
                                    Max. start-up current  -               -                  16 A AC for 10 s
                                    Weight               100 g             90 g               70 g
                                    Dimensions (H x W x D) mm  67 x 50 x 38  60 x 50 x 46     64.5 x 42 x 38
                                    Wiring diagram       (see left)        (see left)         /
                                    Protection rating    IP20              IP20               IP20
                                    Connection           2-pole terminal, max. tightening torque 0.5 Nm: 2.5 mm  solid cable (AWG 14) 1.5
                                                                                               2
           ZR 011
                                                         mm  flexible cable (AWG 16)
                                                           2
                                    Installation         clip for 35 mm DIN rail, EN 60715
                                    Box                  plastic material UL94 V-0, light gray
                  11 12  23 24
                   Load 1  Load 2
               L1       L2          Anti-interference    N in accordance with VDE 0875
               N1       N2
           Normally closed: heating resistor  Values between parentheses = inductive load cos ϕ = 0.8
           Normally open: air conditioning
           unit, filter fan or heat exchanger
                                    Ordering information
                                                                Temperature  Type         Order code      Pack
           ETR 011                  FZK 011                     +5 ° to +60 °C  ACC818079  4TBJ818079R0100  1
                                    FZK 011                     -20 ° to +35 °C  ACC818269  4TBJ818269C0100  1
                                    ZR 011                      0 ° to +60 °C  ACC818217  4TBJ818217R0100  1
                                    (1) At an ambient temperature of 20°C

                  Heating
                  Fan, cooling
                  element, alarm signal