132 GENER AL PURPOSE ENCLOSURES HE AV Y DUT Y AND INDUSTRIAL ENCLOSURES
—
Accessories
Thermostat
Function
Preset thermostat FTO 011
Thermostat with normally-open contact (red casing) for regulating heating resistors or trig-
gering signaling in the event of temperature thresholds being exceeded. The contact is
opened when the temperature increases.
FTO 011 Preset thermostat FTS 011
Thermostat with normally-open contact (blue casing) for regulating filter fans, heat
exchangers and air conditioning units or for triggering signals when the temperature
threshold is exceeded. The contact is closed when the temperature increases.
Technical specifications
Type
Heat sensor with bimetal element
Contact type snap switching
Life cycle > 100,000 cycles
FTS 011
Power 250 V AC, 5 (1.6) A
120 V AC, 10 (2) A
30 W DC
Max. start-up current 16 A AC for 10 s
Connection 2-pole terminal, max. tightening torque 0.8 Nm:
2.5 mm flexible/solid cable (AWG 14)
2
Attachment clip for 35 mm DIN rail, EN 60715
Box plastic material UL94 V-0, light gray
Dimensions 47 x 33 x 33 mm
Weight ca 30 g
Connection diagram Installation mandatory
Operating/storage temperature -40 to +80°C (-40 to +176°F) / -45 to +80°C (-49 to +176°F)
Thermostat FTO 011 Operating/storage humidity max. 90% RH (condensation-free)
Protection rating IP20
Certification VDE, UL File No. E164102, EAC (Eurasian Conformity)
Ordering information
Contact Temperature Type Order code Pack
FTO 011 NC 5 ° to 15 °C ACC818259 4TBJ818259C0100 1
NC 15 ° to 25 °C ACC818260 4TBJ818260C0100 1
NC 0 ° to 10 °C ACC818261 4TBJ818261C0100 1
Thermostat FTS 011
FTS 011 NO 40 ° to 50 °C ACC818262 4TBJ818262C0100 1
NO 50 ° to 60 °C ACC818263 4TBJ818263C0100 1
NO 25 ° to 35 °C ACC818264 4TBJ818264C0100 1
Heating
Fan, cooling ele-