Timers                                                              Timing Diagrams Overview




        Cycle 1 (power start, OFF first)                        Cycle 2 (signal start, OFF first)
        When voltage is applied to the coil, the contacts remain in the off state and the   Voltage is applied to the coil at all times. When a start signal is supplied, the
        set time begins. At the end of the set time, the contacts transfer to the on state   relay contacts remain in the off state and the set time begins. At the end of the
        and remain in the on state until the set time elapses. The timer cycles between   set time, the contacts transfer to the on state and remain in the on state until
        the two states until power is removed from the coil. Removing the coil voltage   the set time elapses. The timer cycles between the two states until the timer   Switches & Pilot Lights
        resets the timer. The set time for both the on state and the off state is the   is reset. The set time for both the on state and the off state are the same. The
        same. Applicable models: GT3A-1, -2, -3, GT3D-1, -2, -3, -4 and RTE-P(B)1.   timer is reset by application of a reset input or by removing coil voltage. Ap-
                                                               plicable models: GT3A-4, GT3D-4 and RTE-P(B) 2.
                 Power
                                                                        Start Input

                 Output
                            T       T       T                             Output
                                                                                     T       T       T
            Type No.    GT3A-1, -2, -3  GT3D-1, -2, -3, -4  RTE-*1                                                     Display Lights
         Mode               C           1-C           C            Type No.      GT3A-4       GT3D-4       RTE-*2
         See Page          805          813          798        Mode               B           2-B           B
                                                                See Page          805          813          798

        Cycle 3 (power start, ON first)
        When voltage is applied to the coil, the contacts immediately transfer to the on   One Shot Cycle (signal start)
        state and the set time begins. At the end of the set time, the contacts transfer
        to the off state and remain in the off state until the set time elapses. The timer   Voltage is applied to the coil at all times. When a start signal is supplied, the con-
        cycles between the two states until power is removed from the coil. Removing   tacts remain in the off state and the set time begins. At the end of the set time,
        the coil voltage resets the timer. The set time for both the off state and the   the contacts transfer to the on state and remain in the on state for the set time.
        on state is the same. Applicable models: GT3A-1, -2, -3, GT3D-1, -2, -3, -4 and   After the set time has elapsed, the contacts return to the off state. The contacts   Relays & Sockets
        RTE-P(B)1.                                             remain in the off state until the timer is reset. The timer is reset by application of
                                                               a reset input or by removing coil voltage. Applicable models: GT3A-5 and GT3D-4.

                 Power
                                                                        Start Input

                 Output
                                                                          Output
                            T       T       T
                                                                                     T       T
            Type No.    GT3A-1, -2, -3  GT3D-1, -2, -3, -4  RTE-*1
                                                                     Type No.          GT3A-5            GT3D-4        Timers
         Mode               D           1-D           D
                                                                Mode                     B                2-F
         See Page          805          813          798
                                                                See Page                 805              813
        One Shot 1 (signal start, retriggerable)
                                                               One Shot 2 (signal start)
        Voltage is applied to the coil at all times. When a start signal is supplied, the
        contacts immediately transfer to the on state and the set time begins. If another   Voltage is applied to the coil at all times. When a start signal is supplied, the
        start signal is supplied (before set time has elapsed) the set time restarts,   contacts immediately transfer to the on state and the set time begins. If another
        as the contacts remain in the on state. Successive pulses at a frequency   start signal is supplied (before set time has elapsed), the set time will not be
        greater than the set time will cause the contacts to remain in the “On state”   affected. When the set time has elapsed, the contacts transfer back to the off   Terminal Blocks
        indefi nitely. When the set time has elapsed the contacts transfer back to the off   state. The contacts remain in the off state until the next start signal is supplied
        state. The contacts remain in the off state until the next start signal is supplied   (no reset is necessary). The timer can be reset by application of a reset input or
        (no reset is necessary). The timer can be reset by application of a reset input or   by removing coil voltage. Applicable models: GT3A-6, GT3D-4, and RTE-P(B)2.
        by removing coil voltage. Applicable models: GT3A-6 and GT3D-4.
                                                                        Start Input
                 Start Input

                                                                          Output
                                                                                      T            T
                   Output
                             T     T          T
                                                                   Type No.      GT3A-6       GT3D-4       RTE-*2       Circuit Breakers
              Type No.          GT3A-6            GT3D-4        Mode               C           3-E           F
         Mode                     A                3-C          See Page          805          813          798
         See Page                 805              813              1.  T = set time, T’ = shorter than set time, Ts = one shot output time
                                                                    2.  For more detailed timing diagrams, see specifi cations for individual timer models.


                                            USA: 800-262-IDEC          Canada: 888-317-IDEC                        795