Timing Diagrams Overview                                                             Timers



        Signal ON/OFF-Delay 1                                  Signal ON/OFF-Delay 2
     Switches & Pilot Lights  supplied, the contacts immediately transfer to the on state and the set time be-  supplied, the contacts remain in the off state and the set time begins. When
                                                               Voltage is supplied to the coil at all times. When a maintained start signal is
        Voltage is supplied to the coil at all times. When a maintained start signal is
        gins. When the set time has elapsed, the contacts transfer to the off state. The
                                                               the set time has elapsed, the contacts transfer to the on state. The contacts
        contacts remain in the off state until the start signal is removed. The contacts
                                                               remain in the on state until the start signal is removed. Once the start signal
        transfer back to the on state and remain in the on state for the set time. When
                                                               is removed, the contacts remain in the on state and the set time begins again.
                                                               Once the set time has elapsed, the contacts transfer back to the off state. The
        the set time has elapsed, the contacts transfer to the off state and remain in the
        off state until the start signal is supplied again (no reset is necessary). The timer
        is reset by application of a reset input or by removing coil voltage. Applicable
                                                               reset signal or removal of power. Applicable models: GT3A-5 and GT3D-4.
        models: GT3A-4, GT3D-4 and RTE-R(B)2.                  timer is ready for the next start signal. The timer is reset by the application of a
                                                                           Start Input
                    Start Input                                              Output
     Display Lights   Output    T          T                         Type No.          T GT3A-5   T      GT3D-4


                                                                                         C
                                        2-C
         Mode Type No.    GT3A-4       GT3D-4       RTE-*2      Mode                     805              3-A
                            C
                                                      D
                                                                                                          813
                                                                See Page
         See Page          805          813          798
                                                               Signal OFF-Delay 1
        Signal ON/OFF-Delay 3
                                                               Voltage is applied to the coil at all times. When a start signal is supplied, the
                                                               contacts immediately transfer to the on state. The set time begins when the
        Voltage is supplied to the coil at all times. When a momentary start signal is
     Relays & Sockets  supplied, the contacts remain in the off state and the set time begins. When the   start signal is removed. When the set time has elapsed, the contacts transfer
        set time has elapsed, the contacts transfer to the on state. The contacts remain
                                                               to the off state. The contacts remain in the off state until the next start signal is
        in the on state until another momentary input is supplied. The contacts then
                                                               supplied (no reset is necessary). The timer can be reset by application of a reset
                                                               input or by removing coil voltage. Applicable models: RTE-P(B)2, GT3A-4, and
        remain in the on state for the set time. When the set time has elapsed, the con-
        tacts transfer to the off state and remain in the off state until the start signal is
        supplied again (no reset is necessary). The timer is reset by application of a reset   GT3D-4.
        input or by removing coil voltage. Applicable models: GT3A-6 and GT3D-4.   Start Input
                    Start Input
                                                                             Output
                                                                                                  T
                      Output
     Timers                     T          T                    Mode Type No.    GT3A-4       GT3D-4       RTE-*2
                                                                                               2-D
                                                                                   D
                                                                                                             E
              Type No.
                                                  GT3D-4
                                GT3A-6
                                                                See Page          805          813          798
         Mode                     D                3-F
         See Page                 805              813         Signal OFF-Delay 2
        One Shot ON-Delay (signal start)                       Voltage is applied to the coil at all times. When a maintained start signal is sup-
                                                               plied, the contacts remain in the off state. When the “start signal is removed”,
        When voltage is applied to the coil, the preset time is initiated and the contacts   the contacts transfer to the “On state” and the set time begins. When the set
     Terminal Blocks  contacts transfer to the on state, and remain in the on state until the start input   the off state until the next start signal is supplied (no reset is necessary. The
        remain in the off state for the preset time. Following the preset time, the
                                                               time has elapsed, the contacts transfer back to the off state. They remain in
                                                               timer can be reset by application of a reset input or by removing coil voltage.
        is supplied. Following the start input, the contacts transfer to the off state for
                                                               Applicable models: GT3A-5 and GT3D-4.
        the preset time. After the preset time has elapsed, the contacts transfer back to
        the on state and remain there until either the next start input is supplied or the
        timer is reset. The timer can be reset by either a reset input or removal of the   Start Input
        coil voltage. Applicable models: GT3A-6 and GT3D-4.
                                                                             Output
                    Start Input
                                                                                                  T      GT3D-4
                                                                                       GT3A-5
                                                                     Type No.
     Circuit Breakers  Type No.  Output  GT3A-6   GT3D-4        Mode                     805              813
                                                                                         D
                                                                                                          3-B
                                   T
                                                                See Page
                                  B
         Mode
                                                   813
         See Page                 805              3-D              1.  T = set time, T’ = shorter than set time, Ts = one shot output time
                                                                    2.  For more detailed timing diagrams, see specifi cations for individual timer models.