RTE Series Timers
RTE Series — Analog Timers
Key features of the RTE series include:
Switches & Pilot Lights • 20 time ranges and 10 timing functions
Time delays up to 600 hours
•
•
Space-saving package
•
High repeat accuracy of ± 0.2%
•
Standard 8- or 11-pin and 11-blade termination
•
2 form C delayed output contacts
• ON and timing OUT LED indicators
• 10A Contact Rating
Cert. No. E9950913332316 (EMC, RTE) UL Listed
Display Lights General Specifications Contact Ratings
File No. E66043
Cert. No. BL960813332355 (LVD, RTE)
Operation System
(Delay output)
Multi-Mode
Operation Type Solid state CMOS Circuit Contact Configuration 2 Form C, DPDT
Time Range 0.1sec to 600 hours Allowable Voltage / 240V AC, 30V DC / 10A
Allowable Current
Pollution Degree 2 (IE60664-1)
Over voltage category III (IE60664-1) Maximum Permissible 1800 cycles per hour
Operating Frequency
AF20 100-240V AC(50/60Hz) Resistive 10A 240V AC, 30V DC
Relays & Sockets D12 12V DC Rated Inductive 7A 240V AC, 30V DC
AD24
Rated Operational Voltage
24V AC(50/60Hz)/24V DC
Load
Horse Power
AF20
85-264V AC(50/60Hz)
1/6 HP 120V AC, 1/3 HP 240V AC
Rating
AD24
Voltage Tolerance
10.8-13.2V DC
D12 20.4-26.4V AC(50/60Hz)/21.6-26.4V DC Life Electrical 500,000 op. minimum (Resistive)
Input off Voltage Rated Voltage x10% minimum Mechanical 50,000,000 op. minimum
Ambient Operating Temperature -20 to +65ºC (without freezing)
Ambient Storage and Transport Temperature -30 to +75ºC (without freezing)
Relative Humidity 35 to 85%RH (without condensation)
Atmospheric Pressure 80kPa to 110kPa (Operating), 70kPa to 110kPa (Transport)
Timers Reset Time 100msec maximum
Repeat Error
±0.2%, ±20msec*
Voltage Error ±0.2%, ±20msec*
Temperature Error ±0.5%, ±20msec*
Setting Error ±10% maximum
Insulation Resistance 100MΩ minimum (500V DC)
Between power and output terminals: 2000V AC, 1 minute
Dielectric Strength Between contacts of different poles: 2000V AC, 1 minute
Terminal Blocks Vibration Resistance 10 to 55Hz amplitude 0.5mm hours in each of 3 axes
Between contacts of the same pole:1000V AC, 1 minute
2
Operating extremes: 98m/sec (10G)
2
Damage limits: 490m/sec (50G)
Shock Resistance
3 times in each of 3 axes 2
Degree of Protection IP40 (enclosure) (IEC60529)
TYPE RTE-P1, -B1 RTE-P2, -B2
120V AC/60Hz 6.5VA 6.6VA
Power Consumption AF20
240V AC/60Hz
(Approx.) 24V AC 60Hz/DC 11.6VA 11.6VA
Circuit Breakers Mounting Position D12 RTE-P1, P2 1.6W 1.6W
3.5VA/1.7W
3.4VA/1.7W
Free
40Hx 36W x 77.9D mm
Dimensions
40Hx 36W x 74.9D mm
RTE-B1, B2
RTE-P1 RTE-P2 RTE-B1, -B2 *For the value of the error against a preset
Weight (Approx.) time, whichever the largest. applies.
87g 89g 85g