Page 50 - IDEC timer catalogue
P. 50
GT3 Series Instructions Timers
Instructions: Wiring Inputs for GT3 Series
Switches & Pilot Lights To avoid electric shock, do not touch the input signal terminal during power voltage application.
Inputs Inputs
When connecting the input signal terminals of two or more GT3A timers to the same contact or transistor, the input terminals of the same number should be con-
nected. (Connect Terminals No.2 in common.)
[Incorrect]
Input
Timer
Contact or Transistor GT3 Series [correct]
Input Input
Terminal Terminal
2 10 Power 2 10 Power
Input Input
Terminal Terminal
2 10 2 10
Display Lights In a transistor circuit for controlling input signals, with its primary and secondary power circuits isolated, do not ground the secondary circuit.
GT3 Series
Timer
Input
Terminal
Power
Rectifier
Circuit Circuit
Insulating Transformer
Relays & Sockets Connect the input signal terminals of the GT3A timers to Terminal No.2 only. Never apply voltage to other terminals; otherwise, the internal circuit may be damaged.
R
Y
5, 6, and 7
Input Terminal
2
10
Power
Input signal lines must be made as short as possible and installed away from power cables and power lines. Use shielded wires or a separate conduit for
input wiring.
Timers
Terminal Blocks
Circuit Breakers
840 www.idec.com