Page 15 - In-line-II-Vertical-Strips
P. 15

INTRODUCTION                                                                  15



          —

          Electronic Fuse Monitoring


          Real time monitoring and easy serviceability


                                                                                                                       01


                  The Electronic Fuse Monitor (EFM) gives a
                  remote alarm at any fault conditions if a
                  fuse is blown and allows faults to be located
                  quickly.

                  •   The EFM unit is self-supplied, which
                      means no additional power supply is
                      required
                  •   The EFM functionality is available up to
                      800 V AC
                  •   The fuse status is also visible on the                                  —
                      product, with red and green LEDs                                        InLine II with Electronic
                                                                                              Fuse Monitor (EFM)





                                      L1
                                      L2
                                      L3
                                      (N)
                   Q1                 PE (N)



















                                               K1                 X1
                                                                  3NO
                                                                  1NC  Q1= Fuse switch disconnector
                                                                      K1= Fuse monitor (EFM)
                                                                      V1= Fuses ok
                                                                  2NC
                                                                  4NO  V2= Fuse(s) blown
                                                                      X1= Multiplug terminals
                                           V1  V2    Q1 in open state




          Fuse status                                    Relay contacts             Relay contacts
                              Green LED     Red LED      NO contact 11,12           NC contact 13,12
          1. ON position                                 Open          Closed       Open          Closed
          Fuses OK                                     X                                        X
          Fuses BLOWN                                                X            X
          2. OFF position
          Fuses OK                                     X                                        X
          Fuses BLOWN                                  X                                        X
   10   11   12   13   14   15   16   17   18   19   20