20               INLINE II  ZLBM/ZHBM/BZL/BZH



          —

          Technical data


          ZLBM/ZHBM/BZL/BZH










          —
                                             ZLBM/ZHBM800  ZLBM/ZHBM1250  ZLBM910A      BZL/ BZH1250A BZL/ BZH2000A
          For NH fuse links
          acc. to IEC60269-2                 2             3              3             -           -
          Rated operational voltage Ue.  (V AC)  500       500            400           690 / 500   690 / 500
          Rated operational current Ie.  (A)  800          1250           910           1250        2000
          Rated insulation voltage Ui.  (V AC)  1000       1000           1000          1000        1000
          Rated impulse withstand voltage
          Uimp.                  (kV)        8             8              8             8           8
          Fuse protected short
          circuit withstand current  (kArms)  100          100            25            -           -
          Fuse protected short
          circuit making.        (kArms)     100           100            25            -           -
          Short-time withstand                                                          20 kA (3P)
          current – 1sec (rms)   (kA)        -             -              -             15 kA (1P)  30 kA
          Short-circuit making
          capacity (peak)        (kA)        -             -              -             20          30
                                 400 V AC    -             -              AC-22B        -           -
                                 500 V AC    AC 21B        AC 21B         -             AC-22B      AC-22B
          Rated making and
          breaking capacity      690 V AC    -             -              -             AC-21B      AC-21B
          Rated frequency        (Hz)        50 / 60       50 / 60        50 / 60       50 / 60     50 / 60
          Total power loss at Ith  (W)       139,7         270            179,4         292,2       594,9
          Max permis. Power loss pr fuse
          link                   Pv (W)      34            48             69            -           -
                                 Open        IP20          IP20           IP20          IP20        IP20
          Degree of protection from the
          front.                 Closed      IP30          IP30           IP30          IP30        IP30
          Electrical durability,
          operating cycles       -           100           100            100           100         100
          Mechanical durability, operating
          cycles                 -           500           500            500           500         500
          Type tested according to EN/IEC 60947-3
          The ambient air temperature must not exceed 40°C and its average over a period of 24h must not exceed 35°C