ZLBM/ZHBM Fuse switch disconnectors
01
—
ZLBM 00-100 ZLBM 00 / ZHBM 00 ZLBM / ZHBM 1 ZLBM / ZHBM 2 ZLBM / ZHBM 3
For NH fuse
links acc. to
IEC60269-2 00 00 1 1/2 3
500 / 690 / 400 / 500 / 400 / 500 / 400 / 500 / 400 / 500 /
Tested with gG fuse 800 690 690 690 690
Rated Tested with gS fuse 800 - 800 800 800
operational
voltage Ue. (V AC) Tested with aR fuse - 1000 1000 1000 1000
160 / 125 /
Tested with gG fuse 63 160 / 160 / 125 250 400, 250 (NH1) 630
Rated Tested with gS fuse 125 - 200 400 400
operational
current Ie. (A) Tested with aR fuse - 125 250 400 630
Rated insulation
voltage Ui. (V AC) 1000 1000 1000 1000 1000
Rated impulse
withstand
voltage Uimp. (kV) 8 8 8 8 8
Fuse protected Tested with gG fuse 100 / 100 / 50 100 / 100 / 100 100 / 100 / 100 100 / 100 / 100 100 / 100 / 100
short circuit Tested with gS fuse 120 - 100 100 50
withstand
current (kArms) Tested with aR fuse - 120 120 120 120
100 / 100 /
Tested with gG fuse 50 100 / 100 / 100 100 / 100 / 100 100 / 100 / 100 100 / 100 / 100
Fuse protected Tested with gS fuse 120 - 100 100 50
short circuit
making. (kArms) Tested with aR fuse - 120 120 120 120
400 V AC - AC-23B AC-23B AC-23B AC-23B
500 V AC AC-23B AC-22B AC-22B AC-22B AC-22B
690 V AC AC-22B AC-21B AC-21B AC-21B AC-21B
Rated making 800 V AC AC-22B - AC-22B AC-22B AC-22B
and breaking
capacity 1000 V AC - AC-22B AC-22B AC-22B AC-22B
Rated frequency (Hz) 50/60 50/60 50/60 50/60 50/60
Total power loss
at Ith (W) 33,4 30,8 / 33,6 36,2 / 37,8 52,2 / 55,5 91,3 / 97,2
Degree of Open IP20 IP20 IP20 IP20 IP20
protection from
the front. Closed IP30 IP30 IP30 IP30 IP30
Electrical
durability,
operating cycles - 200 200 200 200 200
Mechanical
durability,
operating cycles - 1400 1400 1400 800 800
Type tested according to EN/IEC 60947-3