Page 22 - In-line-II-Vertical-Strips
P. 22

22               INLINE II  ZLBM/ZHBM/BZL/BZH



          —

          Technical data


          InLine II Cu+










          —
                                   ZHBM2-T  ZHBM3-T  ZHBM1250-T  BZH1000A-T  BZH1600A-T  BZH2000A-T  BZH1600A-S-T-3P-MB
          For NH fuse links acc. to
          IEC60269-2               1/2      3        3          -         -          -           -
          Single switch/ double
          switch                   Single   Single   Double     Single    Double     Double      Single
          Rated operational        400/500  400/500
          voltage Ue.      (V AC)  /690     /690     500        690       690        500/690     690
          Rated operational current
          Ie.              (A)     400      630      1250       1000      1600       2000        1600
          Rated insulation voltage
          Ui.              (V AC)  1000     1000     1000       1000      1000       1000        1000
          Rated impulse withstand
          voltage Uimp.    (kV)    8        8        8          8         8          8           8
          Fuse protected short
          circuit withstand current (kArms)  100  100  100      -         -          -           -
          Rated short time
          withstand current 1 sec.  (kArms)  -  -    -          15 (1P)   30         30          40
                           400 V AC  AC-23B  AC-23B   -         -         -          -           -
                           500 V AC  AC-22B  AC-22B  AC-21B     -         -          AC-22B      -
                           690 V AC  AC-21B  AC-21B  -          AC-22B    AC-21B     AC-21B      AC-20B
          Rated making and
          breaking capacity  800 V AC  -    -        -          -         -          -           -
          Rated frequency  (Hz)    50/60    50/60    50/60      50/60     50/60      50/60       50/60
          Total power loss at Ith,
          incl. Terminal kit  (W)  70,4     122,9    412,8      183,8     288,9      367,6       -
          Total power loss at Ith  (W)  57,8  102,9  654,9      253,3     516,2      597,9       300,0
          Max permis. power loss
          per fuse link    Pv (W)  34       48       48         -         -          -           -
          Degree of protection   Open  IP20  IP20    IP20       IP20      IP20       IP20        IP20
          from the front.  Closed  IP30     IP30     IP30       IP30      IP30       IP30        IP30
          Electrical durability,
          operating cycles  -      200      200      100        100       100        100         -
          Mechanical durability,                                                                 600
          operating cycles  -      800      800      500        500       500        500
          Max. cable cross section
          to be connected   (mm 2 )   240   240      -          240       -          -           2x300
          Max. cable cross section
          to be connected splice
          for two parallel cables  (mm 2 )   2x240  2x240  4x240  2x240   4x240      4x240       -
          Type tested according to EN/IEC 60947-3
          The ambient air temperature must not exceed 55°C and its average over a period of 24h must not exceed 50°C
   17   18   19   20   21   22   23   24   25   26   27