Page 13 - MOD
P. 13

TECHNIC AL FE ATURES                                                               13




          —
          S3C-MOD Series


          Technical features









                                                                         S3C-MOD24**            S3C-MOD230
                            Suitable for:                                       MCBs S200 and S300 series
                                                                       RCCBs F200 (up to 100A) and F200 B type (up to 63A)
                                                                                     RCBOs DS201
                                                                                Switch Disconnectors SD200
                            Number of modules                                            1
                            Operating voltage                        24…48 V AC/DC -10% +10%  230-240 V AC -15% +10%
                            Minimum operating voltage                     21,6 V AC/DC           110 V AC
         S3C-MOD
                            Power consumption during operation              <28 VA                <30 VA
                            Power consumption at rest                       <1 VA                 <1,5 VA
                            Closing time                                                <1 s
                            Opening time                                                <1 s
                            Mechanical endurance                                       10000
                            Protecion degree acc. To EN 60529                  IP40 (housing)/IP20 (terminals)
                            Operating temperature (with daily average ≤ +35 °C)      -25 …+60 °C
                            Storage temperature                                      -40 …+70 °C
                            Overvoltage category                                         III
                            Pollution degree acc. to EN 60664                            2
                            Shock resistance acc. to IEC/EN 60068-2-27            25g, 2 shocks, 13ms
                            Vibration resistance acc. to IEC/EN 60068-2-6      1g - 20 cycle at 5… 150 …5 Hz
                            Environmental conditions (damp heat) acc. to IEC/EN   28 cycles with 55°C/90-96% and 25°C/95-100%
                            60068-2-30
                            Terminal type                                              plug-in
                            Cross-section of conductors                              0,2…2,5 mm2
                            Tightening torque                                          0,4 Nm
                            Stripping length of the cable                              5 mm
                            Cable length of the control circuits                        10 m
                            Remote control: close contact*                            Terminal 6
                            Remote control: open contact                              Terminal 5
                            Auxiliary contact                                         Terminal 4
                            Signal contact                                            Terminal 3
                           * In case of MCB trip the remote control inputs are inhibited
                           ** Coupling with S204 or SD204 allowed only in case of DC supply