14 MOD & AR EMPOWER YOUR SYSTEMS, WITH REMOTE CONTROL AND AUTOMATION
—
F3C-AR Series
Technical features
F3C-AR24 F3C-AR230 F3C-AR230 D
Suitable for: RCCBs F200 (up to 100A) and F200 B type (up to 63A)
Number of modules 1
Supply voltage 24…48 V AC/DC 230-240 V AC 230-240 V AC
-10% +10% -15% +10% -15% +10%
Minimum operating voltage 20,4 V AC/DC 110 V AC 110 V AC
Number of automatic reclosing attempts 3
F3C-AR Waiting time between auto-reset attempts 3 s 3 s 30 s
Power consumption during operation <25 VA <30 VA <30 VA
Power consumption at rest <1 VA <1,5 VA <1,5 VA
Closing time <1 s
Opening time <1 s
Mechanical endurance 15000
Protecion degree acc. To EN 60529 IP40 (housing)/IP20 (terminals)
Operating temperature (with daily average ≤ +35 °C) -25 …+60 °C
Storage temperature -40 …+70 °C
Overvoltage category III
Pollution degree acc. to EN 60664 2
Shock resistance acc. to IEC/EN 60068-2-27 25g, 2 shocks, 13ms
Vibration resistance acc. to IEC/EN 60068-2-6 1g - 20 cycle at 5… 150 …5 Hz
Environmental conditions (damp heat) acc. to IEC/EN 28 cycles with 55°C/90-96% and 25°C/95-100%
60068-2-30
Terminal type plug-in
Cross-section of conductors 0,2…2,5 mm2
Tightening torque 0,4 Nm
Stripping length of the cable 5 mm
Cable length of the control circuits 10 m
Remote control: close contact Terminal 6
Remote control: open contact Terminal 5
Auxiliary contact Terminal 4
Alarm contact Terminal 3