          12               ABB  SWITCH-DISCONNECTORS – HIGH PERFORMANCE, COMPACT SOLUTION
         —
         Manual switch-disconnectors OT16...100, UL
         Technical data for non fusible disconnect switches
          Technical data according to UL/CSA, AC ratings
          Switch type                        OT16F    OT25F    OT40F    OT63F   OT80F    OT30F     OT60F   OT100F
                                 Approval  CUL US Listed  CUL US Listed  CUL US Listed  CUL US Listed  CUL US Listed  CUL US Listed  CUL US Listed  CUL US Listed
                                             E63822   E63822  E63822   E63822   E63822   E101914  E101914  E101914
                                 Compliance  UL508    UL508    UL508    UL508    UL508    UL98     UL98     UL98
                                           CSA C22.2   CSA C22.2   CSA C22.2   CSA C22.2   CSA C22.2  CSA C22.2 No.4 CSA C22.2 No.4  CSA C22.2
                                              No.14    No.14   No.14    No.14    No.14                       No.4
          General purpose   pf= 0.7...0.8  -40° to 40   20 A  30 A  40 A  60 A    80 A     30 A     60 A    100 A
          amp rating             °C
          Max. operating voltage              600 V    600 V   600 V    600 V    600 V    600 V    600 V    600 V
          Max. horsepower rating /   pf= 0.4...0.5  240 V  5 HP/15.2 A  7.5 HP/22.0 A  10 HP/28.0 A  15 HP/42.0 A  20 HP/54.0 A  10 HP/28.0 A  20 HP/54.0 A  30 HP/80.0 A
          motor FLA current  Three phase 480 V  10 HP/14.0 A  15 HP/21.0 A  20 HP/27.0 A  30 HP/40.0 A  40 HP/52.0 A  20 HP/27.0 A  40 HP/52.0 A  50 HP/65.0 A
                                 600 V    10 HP/11.0 A  20 HP/22.0 A  25 HP/27.0 A  30 HP/32.0 A  40 HP/41.0 A  30 HP/32.0 A  40 HP/41.0 A  50 HP/52.0 A
                         Single phase 120 V  1 HP/16.0 A  1.5 HP/20.0 A  2 HP/24.0 A  2 HP/24.0 A  2 HP/24.0 A  2 HP/24.0 A  3 HP/34.0 A  5 HP/56.0 A
                                 240 V     2 HP/12.0 A  3 HP/17.0 A  5 HP/28.0 A  7.5 HP/40.0 A  10 HP/50.0 A  5 HP/28.0 A  7.5 HP/40.0 A  15 HP/68.0 A
                                 480 V     5 HP/14.0 A  7.5 HP/21.0 A  10 HP/26.0 A  15 HP/34.0 A  20 HP/44.0 A  –  –  25 HP/55.0 A
                                 600 V    7.5 HP/16.0 A  10 HP/20.0 A  15 HP/27.0 A  15 HP/27.0 A  20 HP/38.5 A  –  –  20 HP/35.0 A
          Short circuit rating    Maximum    30 A  60 A  30 A  60 A  30 A  60 A 100 A 150 A 100 A 150 A  60 A  60 A  150 A  100 A
          with fuse      fuse size
                         Fuse type  J     10 kA  10 kA  10 kA  10 kA  10 kA  10 kA 100 kA  – 100 kA  –  200 kA  200 kA  50 kA 200 kA
                         Fuse type  T     10 kA  10 kA  10 kA  10 kA  10 kA  10 kA 100 kA  – 100 kA  –  200 kA  200 kA  50 kA 200 kA
                         Fuse type  RK1   10 kA  –  10 kA  –  10 kA  –  –  –        –        –        –   –    –
                         Fuse type  RK5*  5 kA  5 kA  5 kA  5 kA  5 kA  5 kA  10 kA  5 kA  10 kA  5 kA  –  –  –  –
                         Fuse type  L       –   –    –   –    –   –   –    –   –    –        –        –   –    –
                         Fuse type  H       –   –    –   –    –   –   –  5 kA  –  5 kA       –        –   –    –
          Endurances
          Min. electrical                  6 000 Oper.  6 000 Oper.  6 000 Oper.  6 000 Oper.  6 000 Oper.  6 000 Oper.  6 000 Oper.  6 000 Oper.
          endurance, pf. 0.75...0.8
          Mechanical endurance            20 000 Oper.  20 000 Oper.  20 000 Oper.  20 000 Oper.  20 000 Oper.  20 000 Oper.  20 000 Oper.  20 000 Oper.
          Terminal lugs                    integrated  integrated  integrated  integrated  integrated  integrated  integrated  integrated
          Copper wire range      60-75 °C   18-8 AWG  18-8 AWG  18-8 AWG  14-4 AWG  14-4 AWG  14-4 AWG  14-4 AWG  8-1/0 AWG
          Torque                 Wire    0.8 Nm/7 lb.in 0.8 Nm/7 lb.in 0.8 Nm/7 lb.in  2 Nm/18 lb.in  2 Nm/18 lb.in 6.2 Nm/55 lb.in 6.2 Nm/55 lb.in 6.2 Nm/55 lb.in
                                 tightening
          * Fuse size 70 A for RK5.