          14               ABB  SWITCH-DISCONNECTORS – HIGH PERFORMANCE, COMPACT SOLUTION
          —
          Manual switch-disconnectors OT160G_, IEC and UL
          Technical data for non fusible disconnect switches
          Technical data according to IEC 60947
          Rated insulation voltage                                 Pollution degree 3       1 000 V
          Dielectric strength                                      50 Hz  1 min.            10 kV
          Rated impulse withstand voltage                                                   12 kV
          Rated thermal current in ambient 35 °C                   In open air              160 A
          and temporarily 40 °C                                    In enclosure             160 A
          ...with minimum cable or bar cross section               Cu                       70 mm²
          Rated operational voltage AC-20 and DC-20                                         1 000 V
          Rated operational current, AC-21A, AC-22A, AC-23A          up to 415 V            160 A
                                                                   500 V                    160 A
                                                                   690 V                    160 A
          Rated operational current / poles in series for          Up to 220 V              160 A/2
          DC-21A, DC-22A, DC23A                                    440 V                    125 A/3
                                                                   680 V                    125 A/4
          Rated operational power, AC-23       The kW-ratings are accurate    230 V         45 kW
                                          for three-phase 1500 R.P.M.    400 V              75 kW
                                          standard asynchronous motors.  415 V              75 kW
                                                                   500 V                    90 kW
                                                                   690 V                    132 kW
          Rated breaking capacity in category AC-23                up to 500 V              1 280
                                                                   690 V                    1 280
          Rated conditional short-circuit current I q (r.m.s.) and   I q 100kA, 500V   Î c  30 kA
          corresponding max. Allowed cut-off current Î c of fuse. The  Max. OFA_fuse size  gG/aM  200 A/200 A
          cut-off current Î c referes to values listed by fuse   I q 100kA, 690V   Î c      24 kA
          manufacturers (single phase test acc. To IEC60269)  Max. fuse size  gG/aM         -/200A
          Rated short-time withstand current  R.M.S.-value I cw    690 V        0.25 s      7 kA
                                                                   690 V           1 s      4 kA
          Rated short-circuit making capacity  Peak value I cm     690 V                    12 kA
          Rated capacitor power           Capacitor ratings        415 V                    65 kVAr
          when no initial charge on the capacitor  limited by fuse links
          Power loss / pole               With rated current                                6.5 W
          Mechanical endurance            Divide by two for operation cycles                20 000 Oper.
          Weight without accessories      3-pole switch                                     1.1 kg/0.5 lb
                                          4-pole switch                                     1.3 kg/0.6 lb
          Standard shaft and mounting depth  Square dimension x length of shaft             6X210 mm
                                          Corresponding mounting depth                      230-248 mm/9.2-9.9 in
          Standard handle                                                                   OHB65J6 Type
          Cu-wire size suitable for terminal  60-75 °C                                      10-70 mm²/ 8-1/0 AWG
          Terminal tightening torque                                                        6 Nm/53 lb·in
          Operating torque                Typical for 3 and 4-pole switches                 4 Nm/35.3 lb·in
          Technical data according to UL98, CSA C22.2 No.4
                                                                          cUL us Listed      UL Recognized
          General purpose amp rating    pf=0.7…0.8            -40° to 40 °C  100 A           125 A
          max. operating voltage                                          600 V              600 V
          Max. horsepower rating/motor FLA current  pf=0.4…0.5  240 V AC  40 HP/104 A        40 HP/104 A
                                        Three phase           480 V AC    75 HP/96 A         75 HP/96 A
                                                              600 V AC    100 HP/99 A        100 HP/99 A
                                        Single phase          240 V AC    20 HP/88 A         20 HP/88 A
                                                              480 V AC    30 HP/66 A         30 HP/66 A
                                                              250 Vdc     20 HP/60 A         20 HP/60 A
          Fuse size/short circuit rating  Fuse type           J           150 A/100 kA       150 A/100 kA
                                                              T           150 A/100 kA       150 A/100 kA
                                                              RK5         60 A/100 kA        60 A/100 kA
          Endurances
          Min. electrical endurance, pf. 0.75 - 0.8                       6 000 Oper. cycles  6 000 Oper. cycles
          Mechanical endurance                                            20 000 Operations  20 000 Operations
          Terminal lug kits                                               integrated         integrated
          Wire range                    Use copper conductors only  60-75 °C  8-1/0 AWG      8-1/0 AWG
          Torque                                              Wire tightening  53 lb.in      53 lb.in
          Weight without accessories    3-pole switch                     0.5 lb             0.5 lb
                                        4-pole switch                     0.6 lb             0.6 lb
          Minimum enclosure dimensions  Height x width x depth            400 x 600 x 230 mm  –
                                                                          15.75 x 23.62 x 9.06 in  –