                           ABB  SWITCH-DISCONNECTORS – HIGH PERFORMANCE, COMPACT SOLUTION
          160              ABB    S W I T C H - D I S C O N N E C T O R S  –  H I G H  P E R F OR M A NC E,  C OM P A C T  S OL UT I ON
          16

          —
          Motorized switch-disconnectors, IEC

          Technical data



          Technical data according to IEC 60947-3
          Switch type                                            OTM40F    OTM63F     OTM80F    OTM100F   OTM125F
          Rated insulation voltage and  rated   Pollution degree 3  800 V    800 V     800 V      800 V     800 V
          operational voltage AC20/DC20
          Dielectric strength                      50 Hz  1 min.   6 kV       6 kV      6 kV       6 kV      6 kV
          Rated impulse withstand voltage                          8 kV       8 kV      8 kV       8 kV      8 kV
          Rated thermal current and rated  Ambient 40 °C  2)  In open air   40 A  63 A  80 A      115 A      125 A
          operational current AC20/DC20                                        Ambient 40 °C  2)  In enclosure  40 A  63 A  80 A  115 A  125 A
                                                      Ambient 60 °C   In enclosure  32 A  50 A  63 A  80 A   100 A
          ..with minimum conductor cross section         Cu      10 mm²     16 mm²    25 mm²     35 mm²    50 mm²
          Rated operational current,  AC-21A           up to 500 V  40 A      63 A      80 A      100 A      125 A
                                                       690 V       40 A       63 A      80 A      100 A      125 A
          Rated operational current,  AC-22A           up to 500 V  40 A      63 A      80 A      100 A      125 A
                                                       690 V       40 A       63 A      80 A      100 A      125 A
          Rated operational current,  AC-23A        up to 415 V    40 A       63 A      80 A       80 A      90 A
                                                       500 V       40 A       63 A      80 A       80 A      70 A
                                                       690 V       40 A      40 A       40 A       40 A      50 A
          Rated operational current /                up to 48 V   40 A/1    63 A/1     80 A/1    100 A/1   125 A/1
          poles in series, DC-21A                      110 V      40A/2     63 A/2     80 A/2    100 A/2   125 A/2
                                                       220 V      40 A/3    63 A/4     80 A/4    100 A/4   125 A/4
          Rated operational current /                up to 48 V   40 A/1    63 A/1     80 A/1    100 A/1   125 A/1
          poles in series, DC-22A                      110 V      40 A/2    63 A/2     80 A/2    100 A/2   125 A/2
                                                       220 V      40 A/4    63 A/4     80 A/4    80 A/4     80 A/4
          Rated operational current /                up to 48 V   40 A/1    63 A/1     80 A/1    100 A/1   125 A/1
          poles in series, DC-23A                      110 V      40 A/2    63 A/2     80 A/2    100 A/2   125 A/2
                                                       220 V      40 A/4    63 A/4     63 A/4    63 A/4     63 A/4
          Rated operational power, AC-23A              230 V      7.5 kW     15 kW     22 kW      22 kW     22 kW
          (These values are given for guidance      400...415 V  18.5 kW     30 kW     37 kW      37 kW     45 kW
          and may vary acc. to the motor               500 V      22 kW      37 kW     37 kW      37 kW     45 kW
          manufacturer)                                690 V      37 kW      37 kW     37 kW      37 kW     45 kW
          Rated breaking capacity, AC-23A           up to 415 V   320 A      504 A     640 A      640 A      720 A
                                                       500 V      320 A      480 A     480 A      480 A     560 A
                                                       690 V      320 A      320 A     320 A      320 A     400 A
          Rated conditional short-circuit  I q 50kA, 415V   Î c  16.5 kA    16.5 kA   16.5 kA    16.5 kA    16.5 kA
          current I cc (r.m.s.) and corresponding      gG/aM   125 A/125 A  125 A/125 A  125 A/125 A  125 A/125 A  125 A/125 A
          max. allowed cut-off current Î c .   I q 18kA, 690V   Î c  11 kA   11 kA     11 kA      11 kA      11 kA
          The cut-off current Î c refers to values     gG/aM   125 A/125 A  125 A/125 A  125 A/125 A  125 A/125 A  125 A/125 A
          listed by fuse manufacturers  I q 50kA, 690V    Î c
          (single phase test acc. to IEC60269)         gG/aM    63 A/63 A  63 A/63 A  63 A/63 A  63 A/63 A  63 A/63 A
          Rated short-time withstand current  r.m.s. -value   I cw  690 V, 1s.     2.5 kA  2.5 kA  2.5 kA  2.5 kA  2.5 kA
          Rated short circuit making capacity  1)  Peak value     I cm  690 V  3.6 kA  3.6 kA  3.6 kA  3.6 kA  3.6 kA
          Rated capacitor power (The capacitor      400...415 V  15 kVAr    25 kVAr   30 kVAr    40 kVAr   50 kVAr
          ratings are limited by the fuse link.)
          Power loss / pole        With related current           1.6 W      2.8 W     3.5 W      4.0 W      6.3 W
          Mechanical endurance     Divide by two for operation   20 000 Oper.  20 000 Oper.  20 000 Oper.  20 000 Oper.  20 000 Oper.
                                   cycles
          Cable size               Cu-wire size suitable       2.5...25 mm²  10...70 mm²  10...70 mm²  10...70 mm²  10...70 mm²
                                                             2x2.5...16 mm²
                                   For terminal clamps          14-4 AWG  8-2/0 AWG  8-2/0 AWG  8-2/0 AWG  8-2/0 AWG
                                                               2x14-6 AWG
          Terminal tightening torque  Counter torque required     6 Nm       6 Nm       6 Nm      6 Nm       6 Nm
                                                                 55 Ib.in   55 Ib.in  55 Ib.in   55 Ib.in   55 Ib.in
          Operating torque         3-pole switches                5 Nm       5 Nm       5 Nm      5 Nm       5 Nm
          Weight without accessories  3-pole                     0.89 kg    0.89 kg   0.89 kg    0.89 kg    0.89 kg
                                   4-pole                        1.00 kg    1.00 kg   1.00 kg    1.00 kg    1.00 kg
          1)  Short circuit duration >50 ms, without fuse protection
          2)  Acc. to IEC 60947-1, § 6.1.1.