          Motorized switch-disconnectors, IEC
          Technical data
          Technical data according to IEC 60947-3
          Switch type                                     OTM160E  OTM200E  OTM250E  OTM315E  OTM400E  OTM630E  OTM800E
          Rated insulation voltage and rated   Pollution degree 3  1 000 V  1 000 V  1 000 V  1 000 V  1 000 V  1 000 V  1 000 V
          operational voltage AC-20, DC-20
          Dielectric strength                   50 Hz  1 min.  10 kV  10 kV  10 kV  10 kV   10 kV   10 kV    10 kV
          Rated impulse withstand voltage                   12 kV   12 kV   12 kV   12 kV   12 kV   12 kV    12 kV
          Rated thermal current and  rated   In open air    200 A   200 A   250 A   315 A  400 A    630 A    800 A
          operational current AC-20, DC-20
          in ambient 40 °C (4)   In enclosure               160 A   200 A   250 A   315 A  400 A    630 A    800 A
          ...with minimum cable cross section        Cu    70 mm²  95 mm²  120 mm²  185 mm²  240 mm²  2x185 mm²  2x240 mm²  04
          Rated operational current, AC-21A       ≤ 500 V   200 A   200 A   250 A   315 A  400 A    630 A    800 A
                                                   690 V    160 A   200 A   250 A   315 A  400 A    630 A    800 A
                                                   1000 V   160 A   200 A   250 A   315 A  400 A    630 A    800 A
          Rated operational current, AC-22A       ≤ 500 V   200 A   200 A   250 A   315 A  400 A    630 A    800 A
                                                   690 V    160 A   200 A   250 A   315 A  400 A    630 A    800 A
                                                   1000 V   160 A   200 A   250 A   315 A  400 A    630 A    800 A
          Rated operational current, AC-23A       ≤ 500 V   160 A   200 A   250 A   315 A  400 A    630 A    800 A
                                                   690 V    160 A   200 A   250 A   315 A  400 A    630 A    800 A
                                                   1000 V   135 A   135 A   135 A   200 A   200 A   400 A    400 A
          Rated operational current /            24...110 V  160 A/2  200 A/2  250 A/2  315 A/1  2)  400 A/1  2)  630 A/1  800 A/1
          poles in series, DC-21A  1)              220 V  160 A/2  200 A/2  250 A/2  315 A/2  2)  400 A/2  2)  630 A/1  800 A/1
                                                   440 V  160 A/3  200 A/3  250 A/3  315 A/3  360 A/3  630 A/2  800 A/2
                                                   660 V   160 A/4  200 A/4  230 A/4  2)  315 A/4  360 A/4  630 A/4  2)  650 A/4  2)
          Rated operational power, AC-23           230 V    48 kW  60 kW   75 kW   100 kW  132 kW  200 kW   250 kW
                                                   400 V    80 kW  110 kW  140 kW  160 kW  220 kW  355 kW   450 kW
          (These values are given for guidance     415 V    88 kW  110 kW  145 kW  180 kW  230 kW  355 kW   450 kW
          and may vary acc. to the motor           500 V   112 kW  132 kW  170 kW  220 kW  280 kW  400 kW   560 kW
          manufacturer)                            690 V   144 kW  200 kW  250 kW  315 kW  400 kW  630 kW   800 kW
          Rated breaking capacity                 ≤ 500 V  1 280 A  1 600 A  2 000 A  2 520 A  3 200 A  5 040 A  6 400 A
          in category AC-23                        690 V   1 280 A  1 600 A  2 000 A  2 520 A  3 200 A  5 040 A  6 400 A
          Rated conditional short-circuit current I q   I q 100kA, 500V   Î c  40.5 kA  40.5 kA  40.5 kA  61.5 kA  61.5 kA  90 kA  90 kA
          (r.m.s.) and corresponding max. allowed   Max. OFA_fuse size
          cut-off current Î c of fuse. The cut-off   gG/aM  315 A/315 A 315 A/315 A 315 A/315 A 500 A/450 A  500 A/450 A 800 A/1 000 A 800 A/1 000 A
          current Î c referes to values listed by fuse   I q  80kA, 690V   Î c  40.5 kA  40.5 kA  40.5 kA  59 kA  59 kA  83.5 kA  83.5 kA
          manufacturers (single phase test acc. To   Max. OFA_fuse size
          IEC60269)                                gG/aM  355 A/315 A 355 A/315 A 355 A/315 A 500 A/500 A 500 A/500 A 800 A/1 000 A 800 A/1 000 A
          Rated short-time withstand current  r.m.s. value I cw  ≤ 1000 V 0.15 s  15 kA  15 kA  15 kA  31 kA  31 kA  38 kA  38 kA
                                              ≤ 1000 V 0.25 s  15 kA  15 kA  15 kA  24 kA   24 kA   36 kA    36 kA
                                                ≤ 1000 V 1 s  8 kA  8 kA    8 kA    15 kA   15 kA   20 kA    20 kA
          Rated short-circuit making capacity  Peak value I cm  ≤ 1000 V  30 kA  30 kA  30 kA  65 kA  65 kA  80 kA  80 kA
          Rated capacitor power when  The capacitor  415 V  80 kVAr  100 kVAr  115 kVAr  145 kVAr  180 kVAr  250 kVAr  310 kVAr
          no initial charge on the capacitor  ratings are limited  500 V  96 kVAr  120 kVAr  135 kVAr  175 kVAr  215 kVAr  300 kVAr  375 kVAr
                                 by the fuse links  690 V  128 kVAr  160 kVAr  190 kVAr  250 kVAr  325 kVAr  450 kVAr  550 kVAr
          Power loss / pole      With rated current         3.2 W    4 W    6.5 W   6.5 W   10 W    25 W     40 W
          Mechanical endurance   Divide by two for      20 000 Oper. 20 000 Oper. 20 000 Oper. 16 000 Oper. 16 000 Oper.  10 000 Oper.  10 000 Oper.
                                 oper. cycles
          Weight without accessories  3-pole switch        5.08 kg  5.08 kg  5.08 kg  7.6 kg  7.6 kg  13.6 kg  13.6 kg
          Terminal bolt size     Metric thread           M8x25 mm  M8x25 mm  M8x25 mm M10x30 mm M10x30 mm  M12x40 mm  M12x40 mm
                                 diameter x length
          Terminal tightening torque  Counter torque      15-22 Nm  15-22 Nm  15-22 Nm  30-44 Nm  30-44 Nm  50-75 Nm  50-75 Nm
                                 required
          Operating torque       3-pole switch              7 Nm    7 Nm    7 Nm   16 Nm   16 Nm    27 Nm   27 Nm
                                 disconnector
          1)  Further ratings on request.
          2)  Category B.
   156   157   158   159   160   161   162   163   164   165   166