ABB    S W I T C H - D I S C O N N E C T O R S  –  H I G H  P E R F OR M A NC E,  C OM P A C T  S OL UT I ON    6 63 3
                           ABB  SWITCH-DISCONNECTORS – HIGH PERFORMANCE, COMPACT SOLUTION



          —
          Manual switch-disconnectors OT160...4000, IEC

          Technical data



          Technical data according to IEC 60947-3                                                                      01
          Switch type                                        OT160EV  OT200E  OT250E  OT315E  OT400E  OT630E  OT800E
          Rated insulation voltage and
          rated operational voltage AC-20, DC-20  Pollution degree 3  1 000 V  1 000 V  1 000 V  1 000 V  V 1 000  1 000 V  1 000 V  02
          Dielectric strength                      50 Hz  1 min.  10 kV  10 kV  10 kV  10 kV  10 kV  10 kV   10 kV
          Rated impulse withstand voltage                      12 kV  12 kV  12 kV   12 kV  12 kV    12 kV   12 kV
          Rated thermal current and                                                                                    03
          rated operational current AC-20, DC-20  In open air   200 A  200 A  250 A  315 A  400 A    630 A   800 A
          in ambient 40 °C  4)    In enclosure                 160 A  200 A  250 A   315 A  400 A    630 A   800 A
          ...with minimum cable cross section           Cu   70 mm²  95 mm²  120 mm²  185 mm²  240 mm²  2x185 mm²  2x240 mm²  04
                                                      ≤ 500 V  200 A  200 A  250 A   315 A  400 A    630 A   800 A
                                                       690 V   160 A  200 A  250 A   315 A  400 A    630 A   800 A
          Rated operational current, AC-21A            1000 V  160 A  200 A  250 A   315 A  400 A    630 A   800 A
                                                      ≤ 500 V  200 A  200 A  250 A   315 A  400 A    630 A   800 A
                                                       690 V   160 A  200 A  250 A   315 A  400 A    630 A   800 A
          Rated operational current, AC-22A            1000 V  160 A  200 A  250 A   315 A  400 A    630 A   800 A
                                                      ≤ 500 V  160 A  200 A  250 A   315 A  400 A    630 A   800 A
                                                       690 V   160 A  200 A  250 A   315 A  400 A    630 A   800 A
          Rated operational current, AC-23A            1000 V  135 A  135 A  135 A   200 A  200 A   400 A    400 A
                                                     24...110 V  160 A/2   200 A/2   250 A/2   315 A/1  2)  400 A/1  2)  630 A/1  800 A/1
                                                       220 V  160 A/2   200 A/2   250 A/2   315 A/2  2)  400 A/2  2)  630 A/1  800 A/1
          Rated operational current /                  440 V  160 A/3   200 A/3   250 A/3   315 A/3   360 A/3   630 A/2   800 A/2
          poles in series, DC-21A  1)                  660 V  160 A/4   200 A/4   230 A/4  2)  315 A/4   360 A/4   630 A/4   2)  650 A/4  2)
          Rated operational current /                  800 V  160 A/5   200 A/5   250 A/5   315 A/5   400 A/5   600 A/5   600 A/5
          poles in series, DC-21B                     1000 V  160 A/6   200 A/6   250 A/6  315 A/6   400 A/6   600 A/6   600 A/6
                                                       230 V  48 kW   60 kW  75 kW  100 kW  132 kW  200 kW  250 kW
                                                       400 V  80 kW  110 kW  140 kW  160 kW  220 kW  355 kW  450 kW
                                                       415 V  88 kW  110 kW  145 kW  180 kW  230 kW  355 kW  450 kW
                                                       500 V  112 kW  132 kW  170 kW  220 kW  280 kW  400 kW  560 kW
          Rated operational power, AC-23  3)           690 V  144 kW  200 kW  250 kW  315 kW  400 kW  630 kW  800 kW
          Rated breaking capacity                     ≤ 500 V  1 280 A  1 600 A  2 000 A  2 520 A  3 200 A  5 040 A  6 400 A
          in category AC-23                            690 V  1 280 A  1 600 A  2 000 A  2 520 A  3 200 A  5 040 A  6 400 A
                                  Iq 100kA, 500V          Î c  40.5 kA  40.5 kA  40.5 kA  61.5 kA  61.5 kA  90 kA  90 kA
          Rated conditional short-circuit current   Max. OFA_fuse size  gG/aM 315 A/315 A 315 A/315 A 315 A/315 A  500 A/450 A  500 A/450 A 800 A/1 000 A 800 A/1 000 A
          I q(r.m.s.) and corresponding max. allowed
          cut-off current Î c. The cut-off current Î c.  Iq 80kA, 690V   Î c  40.5 kA  40.5 kA  40.5 kA  59 kA  59 kA  83.5 kA  83.5 kA
          refers to values listed by fuse manufacturers  Max. OFA_fuse size  gG/aM 355 A/315 A 355 A/315 A 355 A/315 A 500 A/500 A 500 A/500 A 800 A/1 000 A 800 A/1 000 A
          (single phase test acc. to IEC60269)  lq 100kA, 690V
                                  Max. fuse size      gG/aM  250A/250A 250A/250A 250A/250A  -/400A  -/400A  -/630A  -/630A
                                                  ≤ 1000 V 0.15 s  15 kA  15 kA  15 kA  31 kA  31 kA  38 kA  38 kA
          Rated short-time withstand current  r.m.s. value I cw  ≤ 1000 V 0.25 s  15 kA  15 kA  15 kA  24 kA  24 kA  36 kA  36 kA
                                                   ≤ 1000 V 1 s  8 kA  8 kA   8 kA   15 kA  15 kA    20 kA   20 kA
          Rated short-circuit making capacity  Peak value I cm  ≤ 1000 V  30 kA  30 kA  30 kA  65 kA  65 kA  80 kA  80 kA
                                  The capacitor        415 V  80 kVAr  100 kVAr  115 kVAr  145 kVAr  180 kVAr  250 kVAr  310 kVAr
          Rated capacitor power when  ratings are limited  500 V  96 kVAr  120 kVAr  135 kVAr  175 kVAr  215 kVAr  300 kVAr  375 kVAr
          no initial charge on the capacitor  by the fuse links  690 V  128 kVAr  160 kVAr  190 kVAr  250 kVAr  325 kVAr  450 kVAr  550 kVAr
          Power loss / pole       With rated current           3.2 W   4 W   6.5 W   6.5 W  10 W     25 W    40 W
                                  Divide by two for oper.
          Mechanical endurance    cycles                   20 000 Oper. 20 000 Oper. 20 000 Oper. 16 000 Oper. 16 000 Oper.  10 000 Oper.  10 000 Oper.
          Weight without accessories  3-pole switch           1.3 kg  1.3 kg  1.3 kg  2.8 kg  2.8 kg  6.1 kg  6.1 kg
                                  Metric thread
          Terminal bolt size      diameter x length         M8x25 mm M8x25 mm M8x25 mm M10x30 mm M10x30 mm  M12x40 mm  M12x40 mm
          Terminal tightening torque  Counter torque required   15-22 Nm  15-22 Nm  15-22 Nm  30-44 Nm  30-44 Nm  50-75 Nm  50-75 Nm
                                  3-pole switch
          Operating torque        disconnector                 7 Nm   7 Nm   7 Nm   16 Nm   16 Nm   27 Nm    27 Nm
          1)  Further ratings on request.
          2)  Category B.
          3)  These values are given for guidance and may vary acc. to the motor manufacturer.
          4)  Acc. to IEC 60947-1, § 6.1.1.