                           ABB    S W I T C H - D I S C O N N E C T O R S  –  H I G H  P E R F OR M A NC E,  C OM P A C T  S OL UT I ON    65 5
                           ABB  SWITCH-DISCONNECTORS – HIGH PERFORMANCE, COMPACT SOLUTION


          —
          Manual switch-disconnectors OT200...1200, UL

          Technical data for non-fusible disconnect switches



                                                                                                                       01
          Switch type                                       OT200U    OT400U        OT600U      OT800U    OT1200U
                                       Approval           CUL US Listed  CUL US Listed  CUL US Listed  CUL US Listed  CUL US Listed
                                       File #               E101914   E101914       E101914     E101914    E101914     02
                                                              IEC        IEC           IEC        IEC         IEC
                                       Compliance            UL98       UL98          UL98       UL98        UL98
                                                        CSA C22.2 No.4  CSA C22.2 No.4  CSA C22.2 No.4  CSA C22.2 No.4  CSA C22.2 No.4  03
          Technical data according to UL/CSA AC Ratings
          General purpose amp rating   pf= 0.7...0.8   -40° to 40 °C  200 A  400 A    600 A      800 A      1 200 A
          Max. operating voltage                             600 V      600 V         600 V      600 V      600 V      04
          Max. horsepower rating /    pf= 0.4...0.5   240 V  75 HP/192.0 A  125 HP/312.0 A  200 HP/480 A  200 HP/602 A  –
          max. motor FLA current  Three phase  480 V    150 HP/180.0 A  250 HP/302.0 A  450 HP/515.0 A  500 HP/590 A  –
                                       600 V            200 HP/192.0 A  350 HP/336.0 A  500 HP/472.0 A  500 HP/472 A  –
          Short circuit rating with fuse  Fuse type  J  200 kA 100 kA  100 kA      – 100 kA         –          –
                                       T                   – 100 kA       –        – 100 kA         –          –
                              Fuse type  RK5               –    –         –     100 kA  –           –          –
                                       L                   –    –         –        – 100 kA     100 kA      100 kA
          Maximum fuse size                             200 A  350 A    600 A    600 A  800 A    800 A      1 200 A
          Current rating               at 250 V DC           200 A      400 A         600 A         –          –
                                       at 600 V DC           100 A      200 A         200 A         –          –
          DC horsepower rating for 4-pole   at 600 V DC      50 HP      50 HP           -           –          –
          switch
          DC horsepower rating for 2-pole   at 125 V DC      20 HP         -            -           –          –
          switch                       at 250 V DC           40 HP      50 HP         50 HP         –          –
          DC short circuit rating for 4-pole switch  with circuit breaker  10 kA  10 kA  10 kA      –          –
          DC short circuit rating for 2-pole switch  with circuit breaker    14 kA  14 kA  18 kA    –          –
                                       at 250 V DC
                                       with circuit breaker    10 kA    10 kA         10 kA         –          –
                                       at 600 V DC
                                       with class J fuse    100 kA     100 kA        100 kA         –          –
                                       at 250 V DC
                                       ... with fuse size    200 A      400 A         600 A         –          –
          Min. electrical endurance, pf.   oper. cycles      6 000      1 000         1 000       500        500
          0.75...0.8                   Divide by two for   20 000 Oper.  16 000 Oper.  10 000 Oper.  6 000 Oper.  6 000 Oper.
          Mechanical endurance         operation cycles
          Terminal lug kits (optional)  75 °C  wire        OZXA-200  OZXA-400      OZXA-800  OZXA-800/1200  OZXA-1200
          Wire range                                   4-300MCM AWG  2-600MCM AWG  2 x 2-600MCM AWG 4 x 2-600MCM AWG 4 x 2-600MCM AWG
          Torque                       Wire tightening  200 lb.in/22.6 Nm 375 lb.in/42.4 Nm  500 lb.in/56.5 Nm  500 lb.in/56.5 Nm  500 lb.in/56.5 Nm
                                       Lug mounting     72 lb.in/8.1 Nm 240 lb.in/27.1 Nm  480 lb.in/54.2 Nm 443 lb.in/50.1 Nm  443 lb.in/50.1 Nm

          Minimum enclosure            Height x Width x   508x407x178 mm  600x350x200 mm   600x700x300 mm  1220x610x305 mm  700x900x400 mm
          dimensions at rated current  Depth            20.3x16.3x7.1 in  24x14x8 in  24x28x12 in  48.8x24.4x12.2 in  28x36x16 in
          Technical data according to IEC 60947
          Rated insulation voltage and rated   Pollution    1 000 V    1 000 V       1 000 V    1 000 V     1 000 V
          operational voltage AC20/DC20   degree 3
          Dielectric strength  50 Hz, 1 min.                 10 kV      10 kV         10 kV      10 kV       10 kV
          Rated impulse withstand voltage                    12 kV      12 kV         12 kV      12 kV       12 kV
          Rated operational current,  AC-22A           up to 415 V  250 A  400 A      800 A     1 600 A     1 600 A
                                       440...500 V           250 A      400 A         800 A     1 600 A     1 600 A
                                       690 V                 250 A      400 A         800 A     1 600 A     1 600 A
          Rated operational current,  AC-23A        up to 415 V  250 A  400 A         800 A     1 250 A     1 250 A
                                       440 V                 250 A      400 A         800 A     1 250 A     1 250 A
                                       500 V                 250 A      400 A         800 A     1 250 A     1 250 A
                                       690 V                 250 A      400 A         800 A     1 250 A     1 250 A
          Rated conditional short-circuit   Iq 50kA, 690V   Î c  35 kA  50.5 kA      71.5 kA        –          –
          current I q (r.m.s.) and corresponding  Max. OFA_fuse  gG/aM  355 A/315 A  500 A/500 A  800 A/1 000 A  –  –
          max. allowed cut-off current Î c. The  size
          cut-off current Î c refers to values   Iq 80kA, 690V  40.5 kA  59 kA       83.5 kA        –          –
                                        Î c
          listed by fuse      Max. OFA_fuse  gG/aM        355 A/315 A  500 A/500 A  800 A/1 000 A   –          –
          manufacturers (single phase test   size
          acc. to IEC60269)
          Rated short-time withstand current r.m.s. -value I cw 690 V, 1 s    8 kA  15 kA  20 kA  50 kA      50 kA
                                       500/690 V             30 kA      65 kA         80 kA     110 kA  1)  110 kA  1)
          Rated short circuit making capacity Peak value I cm
          Max. distance from switch to                          –         –             –       150 mm     150 mm
          nearest bus bar / cable support mm
          Power loss / pole   At rated operational current   6.5 W      10 W          40 W        29 W       48 W
          Weight without accessories   3-pole            1.5 kg/3.31 lb  3.0 kg/6.61 lb  6.3 kg/13.89 lb  17.2 kg/37.92 lb  17.2 kg/37.92 lb
                                       4-pole            1.9 kg/4.16 lb  3.5 kg/7.72 lb  8.0 kg/17.64 lb  72.2 kg/48.94 lb  72.2 kg/48.94 lb
          Terminal bolt size  Metric thread diameter x length  M8x25 mm  M10x30 mm  M12x40 mm  M12x50 mm  M12x60 mm
          1)  The value is 92 kA for 4-pole switch disconnector.