ABB  SWITCH-DISCONNECTORS – HIGH PERFORMANCE, COMPACT SOLUTION
          64
          64               ABB    S W I T C H - D I S C O N N E C T O R S  –  H I G H  P E R F OR M A NC E,  C OM P A C T  S OL UT I ON


          —
          Manual switch-disconnectors OT160...4000, IEC

          Technical data



          Technical data according to IEC 60947-3
          Switch type                                  OT1000E  OT1250E  OT1600E  OT2000EC  OT2000E  OT2500E  OT3200E  OT4000E
          Rated insulation voltage and
          rated operational voltage AC20/DC20  Pollution degree 3  1 000 V  1 000 V  1 000 V  1 000 V  1 000 V  1 000 V  1  000 V  1 000 V
          Dielectric strength                50 Hz  1 min.  10 kV  10 kV  10 kV  10 kV  10 kV  10 kV  10 kV  10 kV
          Rated impulse withstand voltage                12 kV   12 kV  12 kV  12 kV   12 kV  12 kV  12 kV   12 kV
          Rated thermal current and  Ambient 40 °C  1)  In open air   1 000 A  1 250 A  1 600 A  2 000 A  2 000 A  2 500 A  3 200 A  3 800 A,
          rated operational current AC20/DC20                                                              4000 A  5)
                                Ambient 40 °C  1)  In enclosure  1 000 A  1 250 A  1 600 A  –  –  –     –      –
          ..with minimum conductor cross   Cu         2x300 mm² 2x400 mm² 2x500 mm² 3x500 mm² 3x500 mm² 4x500 mm²  4x1 000   5x1 000
          section                                                                                     mm²    mm²
          Rated operational current, AC-21A           up to 690 V  1 000 A  1 250 A  1 600 A  –  2 000 A  2)  2 500 A  2)  –  –
                                             1000 V     1 000 A  1 250 A  1 600 A  –     –      –       –      –
                                                                                                               2)
          Rated operational current, AC-22A           up to 415 V  1 000 A  1 250 A  1 600 A  2 000 A  2)  2 000 A  2)  2 500 A  2)  3 200 A  2)  3 800 A  ,
                                                                                                              2) 5)
                                                                                                          4000 A
                                                                                               2) 3)
                                                                                        2) 3)
                                             500 - 690 V   1 000 A  1 250 A  1 600 A  – 2 000 A      2 500 A      –  –
          Rated operational current, AC-23A        up to 500 V  1 000 A  1 250 A  1 250 A  –  –  –      –      –
                                             690 V      1 000 A  1 250 A  1 250 A  –     –      –       –      –
          Rated operational power, AC-23A    400...415 V  560 kW  710 kW  710 kW  –      –      –       –      –
          (These values are given for guidance   440 V  630 kW  800 kW  800 kW    –      –      –       –      –
          and may vary acc. to the motor     500 V      710 kW  900 kW  900 kW    –      –      –       –      –
          manufacturer)                      690 V     1 000 kW  1 200 kW  1 200 kW  –   –      –       –      –
          Rated breaking capacity, AC-23A    up to 500 V  10 000 A  10 000 A  10 000 A  –  –    –       –      –
                                             690 V     10 000 A  10 000 A  10 000 A  –   –      –       –      –
          Rated conditional short-circuit current  Iq 80kA, ≤415V  Î c  100 kA  100 kA  100 kA  100 kA  –  –  –  –
          I q (r.m.s.) and corresponding max.   Max. OFA_fuse size  gG/aM  1 250 A/  1 250 A/  1 250 A/  1 250 A/  1 250 A/  –  –  –
          allowed cut-off current Î c.                  1 250 A  1 250 A  1 250 A  1 250 A  1 250 A
          The cut-off current Î c refers to values   Iq 100kA, 500V  Î c  106 kA  106 kA  106 kA  –  –  –  –   –
          listed by fuse manufacturers (single   Max. OFA_fuse size  gG/aM  1 250 A/  1 250 A/  1 250 A/  –  1 250 A/  –  –  –
          phase test acc. to IEC60269).                 1 250 A  1 250 A  1 250 A     1 250 A
          Rated short-time withstand current  r.m.s. -value I cw  690 V, 0.25 s  50 kA  50 kA  50 kA  50 kA  80 kA  80 kA  80 kA  80 kA,
                                                                                                           100 kA  5)
                                             690 V, 1 s    50 kA  50 kA  50 kA  50 kA  55 kA  55 kA  65 kA   80 kA
          Rated short circuit making capacity  Peak value I cm    690 V  110 kA  4)  110 kA  4)  110 kA  4)  110 kA  4)  176 kA  176 kA  176 kA  176 kA,
                                Max. distance from                                                         220 kA  5)
                                switch frame to
                                nearest busbar/         150 mm  150 mm  150 mm  150 mm  150 mm  150 mm  150 mm  150 mm
                                cable support
          Rated capacitor power when  The capacitor  415 V  460 kVAr  575 kVAr  575 kVAr  575 kVAr  –  –  –    –
          no initial charge on the capacitor  ratings are limited  500 V  550 kVAr  690 kVAr  690 kVAr  690 kVAr  –  –  –  –
                                by the fuse links  690 V  750 kVAr  950 kVAr  950 kVAr  950 kVAr  –  –  –      –
          Power loss/pole       At rated operational      19 W   29 W   48 W    48 W   55 W   85 W    95 W  130 W
                                current
          Mechanical endurance  Divide by two for     6 000 Oper. 6 000 Oper. 6 000 Oper. 6 000 Oper. 6 000 Oper. 6 000 Oper. 5 000 Oper. 5 000 Oper.
                                operation cycles
          Weight without accessories  3-pole            14.7 kg  14.7 kg  16.8 kg  16.8 kg  24.9 kg  24.9 kg  31.8 kg  36.2 kg
                                4-pole                  18.8 kg  18.8 kg  21.6 kg  21.6 kg  32.4 kg  32.4 kg  41.5 kg  47.5 kg
          Terminal bolt size    Metric thread           M12x50   M12x50   M12x60   M12x60   M12x60   M12x60   M12x60   M12x60
                                diameter x length         mm     mm      mm     mm      mm     mm     mm      mm
          Terminal tightening torque  Counter torque  50...75 Nm  50...75 Nm  50...75 Nm  50...75 Nm  50...75 Nm  50...75 Nm  50...75 Nm  50...75 Nm
                                required
          Operating torque      3-pole switch-           65 Nm  65 Nm  65 Nm   65 Nm  65 Nm  65 Nm   65 Nm  65 Nm
                                disconnector
          1)  Acc. to IEC60947-1, § 6.1.1.
          2)  IEC 947-3, utilization category B, infrequent operation.
          3)  Phase barriers or terminal shrouds must be used on both sides of the switch at voltages ≥ 500 V.
          4)  The value is 92 kA for 4-pole switch-disconnectors.
          5)   OT4000E_W8