Page 148 - Sace Emax 2 Catalogue
P. 148

7/14             SACE EMA X 2 LOW VOLTAGE AIR CIRCUIT-BRE AKERS



          —

          Installation in switchgear






                           Position                                    Power supply
                           All SACE Emax 2 circuit breakers can be floor   The Emax 2 circuit breakers can be supplied, from
                           mounted in a vertical position inside the switch-  either the upper or lower terminals. In the event a
                           gear compartment.                           measurement module is present, in order to make
                           The E1.2 circuit breaker can also be installed in a   use of all information when the circuit breaker is
                           horizontal position and wall mounted. Conve-  in the open position, the voltage sockets must be
                           niently, the screens of the Ekip Touch and Hi-  installed on the power supply side.
                           Touch versions rotate to a horizontal view for key
                           data when the E1.2 is installed horizontally.






                           Insulation distances and
                           connection
                           The circuit breakers can be connected to the main   Installation of live parts must ensure:
                           power system using the most common configura-  •  Minimum insulation distances between the
                           tions and dimensions of copper bars.         phases

                           Rated insulation voltage Ui                 Minimum distance [mm]
                           1000V                                       for voltages upper to 440V  in fixed circuit breakers,
                                                                       please use phase separators

                           •  Insulation distance of installation cubicle

                           Fixed circuit breakers                      Withdrawable circuit breakers
                                   A       B        C       D                  A       B       C        D
                           [mm]    3p      4P                          [mm]    3p      4P
                           E1.2    250     322      382.5*  130        E1.2    280     350     440*     252
                           E2.2    400     490      500     221        E2.2    400     490     500      355
                           E4.2    500     600      500     221        E4.2    500     600     500      355
                           E6.2    900     1000     500     221        E6.2    900     1000    500      355
                           E6.2/f  -       1200     500     221        E6.2/f  -       1200    500      355
                           * 332.5mm for voltage less ≤ 440V AC        * 390mm for voltage less ≤ 440V AC