INSTALL ATION                                                                     7/9














                           Current-limiting curves                     The current-limiting circuit breakers are distin-
                           The SACE Emax 2 series features a series of cur-  guished by short-time withstand currents Icw
                           rent-limiting circuit breakers in sizes E1.2 up to   that are not particularly high and therefore not in-
                           1600A. These circuit breakers are distinguished   dicated for applications in which chronoampero-
                           constructively by:                          metric selectivity is required with several down-
                           •  Dedicated stored energy operating mechanism,   stream devices or in which devices are present
                            which reduces opening times.               with high inrush current in the start-up stage.
                           •  Specific main contacts that, utilizing the elec-
                            trodynamic forces generated by the short-cir-
                            cuit current, accelerate opening of the main
                            contacts.

                           These features ensure rapid interruption which
                           consequently reduces electromechanical and
                           thermal stress on the system during a short-cir-
                           cuit.