Page 144 - Sace Emax 2 Catalogue
P. 144

7/10             SACE EMA X 2 LOW VOLTAGE AIR CIRCUIT-BRE AKERS



          —

          Installation environment






                           —                                           In addition, ABB provides instructions for the use
                                                                       of circuit breakers in nonstandard environments,
                           SACE Emax 2 circuit breakers                as for example personalized maintenance pro-
                           have been designed and tested in            gram or installation solutions aimed at increasing
                                                                       performances and extending the lifecycle of the
                           accordance with major                       circuit breaker.
                           international Standards to
                           manage the electrical plant.
                                                                       Temperature
                           The installation requirements prescribed by the   SACE Emax 2 circuit breakers can operate in the
                           international Standards are listed below.   following environmental conditions:
                                                 Temperature (°C)
                                                 Operating            Active Display       Storage
                           Emax 2 with Ekip DIP  -25°C … +70°C        -                    -40°C … +70°C
                           Emax 2 with Ekip Touch  -25°C … +70°C      -20°C … +70°C        -30°C … +70°C
                           Emax 2 with LCD       -25°C … +70°C        -25°C … +70°C        -40°C … +70°C
                           Emax 2 swith-disconnectors  -25°C … +70°C  -                    -40°C … +70°C






                           Environmental conditions                    Altitude
                           The devices can be installed in industrial environ-  SACE Emax 2 air circuit breakers do not undergo
                           ments with pollution level 3, IEC60947. SACE   changes in rated performance up to 2000 metres.
                           Emax 2 circuit breakers also comply with:   Beyond this altitude, the properties of the atmo-
                           •  IEC60721-3-6 class 6C3                   sphere in terms of composition, dielectric capaci-
                           •  IEC60721-3-3 class 3C2                   tance, cooling power and pressure can vary and,
                                                                       therefore, the performance of the circuit breakers
                                                                       is subject to derating, which can be measured by
                                                                       means of the variation in maximum rated service
                                                                       voltage and rated uninterrupted current.

                           Altitude                            [m]     2000      3000      4000      5000
                           Rated service voltage - Ue  Versions 690V  [V]  690   624       544       477
                           Rated current                       [% In]  100       98        93        90
   139   140   141   142   143   144   145   146   147   148   149