Page 9 - Sace Emax 2 Manual Touch Protection breakers
P. 9
ABB | SACE Emax 2
2 - Models and Versions
Default functions and Every Ekip Touch module has default measurement and protection functions, which can be extended with the
extensions aid of additional software packages.
The extensions (additional SW packages) can be pre-engineered when the circuit-breaker is ordered or at a
later date (in this case, via ABB Ability Marketplace TM
Overview
Figure 3
Ekip Ekip G Ekip G
Model Ekip Touch
Hi-Touch Touch Hi-Touch
Versions LSI, LSIG LSI, LSIG LSIG LSIG
Standard protections X X X X
Voltage protections O (1) X X (3) X
Voltage advanced protections O (1) O X (3) X
Frequency protections O (1) X X (3) X
Power protections O (1) X (3) X (3) X
ROCOF protections O (1) O O X
Adaptive protections O X O X
Standard Measurements X X X X
Ekip Measuring Measurements O X X X
Class 1 Power & Energy Metering O (2) X X X
Datalogger O (1) X X X
Network Analyzer O (1) X O X
X = Available by default; O = Optional
(1) Configurable if Measuring Measurements package is present
(2) Only available at the time circuit-breaker is ordered
(3) Certain protections of the complete package are available by default; the remaining ones can be activated
on request
Description Lists of the main characteristics of the protections and measurements of each package are given in the next
chapters.
A description of the Datalogger and Network Analyzer functions is available in manual 1SDH001330R1002.
7 | © 2019 ABB | 1SDH001316R1002 - ECN000086501 - Rev. A Overview of Ekip Touch | 2 - Models and Versions