Page 153 - Sace Emax 2 Manual for design engineers
P. 153
Continued from the previous page ABB | SACE Emax 2
4. Extract the disconnection crank from its housing See Figure 56.
5. Press the lock pushbutton and fit the handle into the moving part. In this phase, the moving part will
still be in the DISCONNECT position. See Figure 57.
1
2
Figure 56 Figure 57
6. Keep breaker pushed. Turn handle clockwise until pushbutton projects and signaling device indicates
that circuit-breaker is in position TEST. See Figure 58.
1
2
Figure 58
7. Press the lock button and then rotate the crank clockwise until the button comes out and the indicator
shows that the circuit-breaker is in the CONNECT position. See Figure 59.
1
2
Figure 59
Continued on the next page
151 | © 2020 ABB | 1SDH001330R1002 - ECN000134959 - Rev. A Mechanical characteristics | 1 - E1.2 description