Continued from the previous page ABB | SACE Emax 2
7. Check that the circuit-breaker is open (open / closed indicator "O - OPEN"), and check that the springs
are discharged (spring signalling device "white - DISCHARGED SPRING") as indicated in Figure 47.
Figure 47
Mechanical status indicators The following are the possible states in which you can find the circuit-breaker:
1. Circuit-breaker open with springs discharged (see Figure 48).
2. Circuit-breaker open with springs charged (see Figure 49).
3. Circuit-breaker closed with springs discharged (see Figure 50).
4. Circuit-breaker closed with springs charged (see Figure 51). This state occurs when after closing (see
step 4 - Figure 51) the springs are recharged manually or automatically by the gearmotor (if provided).
Figure 48 Figure 49 Figure 50
Figure 51
149 | © 2020 ABB | 1SDH001330R1002 - ECN000134959 - Rev. A Mechanical characteristics | 1 - E1.2 description