Continued from the previous page                                   ABB | SACE Emax 2
                                      7.  Check that the circuit-breaker is open (open / closed indicator "O - OPEN"), and check that the springs
                                         are discharged (spring signalling device "white - DISCHARGED SPRING") as indicated in Figure 79.


















                                    Figure 79


         Mechanical status indicators The following are the possible states in which you can find the circuit-breaker:
                                      1.  Circuit-breaker open with springs discharged (see Figure 80).
                                      2.  Circuit-breaker open with springs charged (see Figure 81).
                                      3.  Circuit-breaker closed with springs discharged (see Figure 82).
                                      4.  Circuit-breaker closed with springs charged and not ready to close (see Figure 83). This state occurs
                                         when after closing (see step 4 - Manual operations for opening and closing the circuit-breaker) the
                                         springs are recharged manually or automatically by the gearmotor (if provided).
                                      5.  Circuit-breaker open with springs charged and not ready to close (see Figure 84). This state occurs
                                         in the following cases:
                                        •  The circuit-breaker is open due to tripping of protection trip units and the Reset signal has not been
                                          reset. To close the circuit-breaker press the TU Reset pushbutton on the front of the circuit-breaker.
                                        •  The key lock or padlock is active in the open position.
                                        •  The undervoltage coil is de-energized
                                        •  The opening coil is permanently energized.
                                        •  The closing coil is permanently energized.
                                        •  The pushbutton for enabling the insertion/extraction crank of a withdrawable circuit-breaker is pres-
                                          sed.


















                                    Figure 80                 Figure 81                  Figure 82


















                                    Figure 83                 Figure 84