Continued from the previous page                                   ABB | SACE Emax 2
                                      12.  Extract the crank. See Figure 96.
                                      13.  Replace the crank in its housing See Figure 97.




















                                    Figure 96                               Figure 97

                                           WARNING! The inserted circuit-breaker must be opened in order to be able to reach
                                               the test position. On the UL version, the fail safe prevents the removal of the
                                           circuit-breaker from the fixed part with springs charged. Discharge the springs before
                                           removing the circuit-breaker from the fixed part. For further details, consult the
                                           Mechanical safety accessories chapter.
                                    To extract the moving part from the fixed part, perform the same steps indicated for insertion in reverse order.



















                                    Figure 98


                                                                                                  Continued on the next page