                                      8.  Extract the disconnection crank from its housing See Figure 92.
                                      9.  Press the lock pushbutton and fit the handle into the moving part. In this phase, the moving part will
                                         still be in the DISCONNECT position. See Figure 93.








                                                                                                              1



                                                                                                2








                                    Figure 92                      Figure 93
                                      10.  Turn handle clockwise until pushbutton projects and signaling device indicates that circuit-breaker is
                                         in position TEST. See Figure 94.



















                                    Figure 94

                                      11.  Press lock pushbutton and turn handle clockwise until pushbutton projects and signaling device
                                         indicates that circuit-breaker is in position CONNECT. See Figure 95.








                                                                              2




                                                                                               1



                                    Figure 95