Page 162 - Sace Emax 2 Manual for design engineers
P. 162
Continued from the previous page ABB | SACE Emax 2
8. Extract the disconnection crank from its housing See Figure 92.
9. Press the lock pushbutton and fit the handle into the moving part. In this phase, the moving part will
still be in the DISCONNECT position. See Figure 93.
1
2
Figure 92 Figure 93
10. Turn handle clockwise until pushbutton projects and signaling device indicates that circuit-breaker is
in position TEST. See Figure 94.
Figure 94
11. Press lock pushbutton and turn handle clockwise until pushbutton projects and signaling device
indicates that circuit-breaker is in position CONNECT. See Figure 95.
2
1
Figure 95
Continued on the next page
160 | © 2020 ABB | 1SDH001330R1002 - ECN000134959 - Rev. A Mechanical characteristics | 2 - E2.2-E4.2-E6.2 description