                                    To optimize the thermal efficiency, it is recommended to adhere to the following installation
                                    guidelines:
                                     •  Guarantee the maximum possible distance between the input and output busbars. See the example
                                       Figure 113.
                                     •  Guarantee the maximum use of the surface of the terminal. See the example Figure 114.
                                     •  Make sure that the distance between the holes and the end of the terminal and between the holes and
                                       extremity of the busbar is the same. See the example Figure 115.
                                     •  Make sure that, accordingly to the number of busbars and terminal tangs, the busbars of the lateral phases
                                       are as distant as possible from the busbars of the central phase. See the example Figure 116.








                                                                        OK                  NO






                                    Figure 113







                                                                     OK                                 NO








                                    Figure 114







                                                                     OK                                  NO




                                                     =   =                              ≠≠


                                    Figure 115






                                                           OK                           NO








                                                           OK                           NO
                                    Figure 116







       172 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A                         Mechanical characteristics | 4 - Installation