          Derating due to temperature In certain installations, the circuit-breakers could end up operating at a temperature above the reference
                                    temperature (40 °C). In such cases the rated capacity of the circuit-breaker may be reduced. To find out the
                                    percentage of reduction to be applied to the capacity consult the following table:
                                     Emax 2 E1.2 Temperature [°C]
                                                < 40      45       50        55       60        65       70
                                     E1.2 250   100%      100%     100%      100%     100%      100%     100%
                                     E1.2 630   100%      100%     100%      100%     100%      100%     100%
                                     E1.2 800   100%      100%     100%      100%     100%      100%     100%
                                     E1.2 1000  100%      100%     100%      100%     100%      100%     100%
                                     E1.2 1250  100%      100%     100%      100%     100%      100%     100%
                                     E1.2 1600  100%      100%     100%      98%      95%       93%      90%

                                     Emax 2 E2.2 Temperature [°C]
                                                < 40      45       50        55       60        65       70
                                     E2.2 250   100%      100%     100%      100%     100%      100%     100%
                                     E2.2 630   100%      100%     100%      100%     100%      100%     100%
                                     E2.2 800   100%      100%     100%      100%     100%      100%     100%
                                     E2.2 1000  100%      100%     100%      100%     100%      100%     100%
                                     E2.2 1250  100%      100%     100%      100%     100%      100%     100%
                                     E2.2 1600  100%      100%     100%      100%     100%      100%     98%
                                     E2.2 2000  100%      100%     100%      100%     95%       91%      87%
                                     E2.2 2500  100%      100%     100%      100%     98%       94%      90%

                                     Emax 2 E4.2 Temperature [°C]
                                                < 40      45       50        55       60        65       70
                                     E4.2 2000  100%      100%     100%      100%     100%      100%     100%
                                     E4.2 2500  100%      100%     100%      100%     100%      100%     100%
                                     E4.2 3200  100%      100%     97%       93%      89%       86%      82%
                                     E4.2 4000  100%      100%     94%       90%      86%       83%      80%

                                     Emax 2 E6.2 Temperature [°C]
                                                < 40      45       50        55       60        65       70
                                     E6.2 4000  100%      100%     100%      100%     100%      100%     100%
                                     E6.2 5000  100%      100%     100%      100%     100%      98%      95%
                                     E6.2 6300  100%      100%     95%       91%      87%       84%      81%





































       174 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A                 Mechanical characteristics | 5 - Technical characteristics