Page 177 - Sace Emax 2 Manual for design engineers
P. 177

ABB | SACE Emax 2
                Current limiting curve SACE Emax 2 series offer current-limiting circuit-breakers in E1.2 size up to 1600 A. These circuit-breakers
                                    are characterized from the constructional point of view by the following features:
                                     •  Dedicated stored energy operating mechanism that reduces opening times.
                                     •  Specific main contacts that, by exploiting the electrodynamic forces generated by the short-circuit,
                                       accelerate the opening of the main contacts.

                                    These features enable rapid breaking and consequently reduce the electromechanical  and thermal stress
                                    suffered by the installation during a short-circuit. The Current-limiting circuit-breakers are characterized by
                                    short-time withstand currents that are not particularly high and are therefore not suitable for applications
                                    where selectivity towards more downstream devices is required or in case of devices with high inrush currents
                                    in the start-up phase.



























                                    E1.2 L - Current-limiting curves        E1.2 L - Pass-through specific energy limitation curves


















































       175 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A                 Mechanical characteristics | 5 - Technical characteristics
   172   173   174   175   176   177   178   179   180   181   182