Page 249 - Sace Emax 2 Manual for design engineers
P. 249
ABB | SACE Emax 2
S33 M/2: springs charged The S33 M/2 contact signals the state of the closing springs of the circuit-breaker control (charged or
signalling contact discharged).
It is available in two types:
• standard contact
• contact for digital signals
NOTE: the S33_M/2 contact is always included in the gearmotor for automatic charging of
the springs in the standard version. The version for digital signals must be requested
with the order for the motor.
35
36
38
S33
S33 M/2 for E1.2
35
36
38
S33
S33 M/2 for E2.2 - E4.2 - E6.2
The following table provides information on the electrical characteristics:
Characteristics Standard Digital signals
24V - 0.1 A
DC 125V 0.5A @ 0ms / 0.3A @ 10ms -
250V 0.3A @ 0ms / 0.15A @ 10ms -
3A cos φ 0.3 -
Breaking 250V 5A cos φ 0.7 -
capacity
5A cos φ 1 -
AC
3A cos φ 1 -
400V 2A cos φ 0.7 -
1A cos φ 0.3 -
Minimum load 100mA @ 24V 1mA @ 5V
S33/M2: Connections
More details are available in the website http://www.abb.com/abblibrary/DownloadCenter/, which also
includes the entire circuit diagram 1SDM000091r0001.
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/,
in particular for E1.2 in the kit sheet 1SDH000999r0609 and for E2.2-E4.2-E6.2 in the kit sheet
1SDH001000r0609.
247 | © 2020 ABB | 1SDH001330R1002 - ECN000134959 - Rev. A Electrical accessories | 2 - Electrical signalling accessories