ABB | SACE Emax 2
      AUP: auxiliary position contacts The AUP contacts are intended for circuit-breakers in withdrawable version.
                                    They electrically signal the position of a moving part (inserted/test/withdrawn) in relation to the fixed part in
                                    which they are inserted.
                                    These are "switching" contacts and are available in the following configurations:
                                    Up to a maximum of six contacts for E1.2:
                                     •  six standard contacts
                                     •  six digital signals
                                    Up to a maximum of ten contacts for E2.2-E4.2-E6.2:
                                     •  five standard contacts
                                     •  five digital signals
                                     •  five additional standard contacts
                                     •  five additional digital signals













                                    AUP for E1.2                            AUP for E2.2 - E4.2 - E6.2
                                    The following table provides information on the electrical characteristics:
                                     Characteristics               Standard                  Digital signals
                                                         24V       -                         0.1 A
                                                  DC     125V      0.5A @ 0ms / 0.3A @ 10ms  -
                                                         250V      0.3A @ 0ms / 0.15A @ 10ms  -
                                                                   3A cos  φ 0.3             -
                                     Breaking            250V      5A cos  φ 0.7             -
                                     capacity
                                                                   5A cos  φ 1               -
                                                  AC
                                                                   3A cos  φ 1               -
                                                         400V      2A cos  φ 0.7             -
                                                                   1A cos  φ 0.3             -
                                     Minimum load                  100mA @ 24V               1mA @ 5V


                                    AUP: Connections
                                    More details are available in the website http://www.abb.com/abblibrary/DownloadCenter/, which also
                                    includes the entire circuit diagram 1SDM000091r0001.
                                    Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/,
                                    in particular for E1.2 in the kit sheet  1SDH000999r0603 and for E2.2-E4.2-E6.2 in the kit sheet
                                    1SDH001000r0603.



























       243 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A                Electrical accessories | 2 - Electrical signalling accessories