        RTC: ready to close signalling  The RTC contact indicates that the circuit-breaker is ready to receive a closing command.
                            contact  The conditions necessary to allow the closing of the circuit-breaker are:
                                     •  circuit-breaker open
                                     •  springs charged
                                     •  absence of an opening command or of a lock in opening

                                           NOTE: if the circuit-breaker is opened due to the tripping of the Ekip protection trip unit, in
                                               order to allow closing, the Reset signal of the circuit-breaker must have been reset (press
                                           the TU Reset pushbutton on the front panel).
                                    The RTC is a "switching" contact type and is available in the standard version or in the versions for digital
                                    signals.


                                                            45

                                                            46
                                                            48
                                                           RT C


                                    RTC for E1.2



                                                      45

                                                      46
                                                      48
                                                      RT C


                                    RTC for E2.2 - E4.2 - E6.2
                                    The following table provides information on the electrical characteristics:
                                     Characteristics               Standard                  Digital signals
                                                         24V       -                         0.1 A
                                                                   0.3A @ 0ms                -
                                                         125V
                                                  DC               0.15A @ 10ms              -
                                     Breaking            250V      0.3A @ 0ms                -
                                     capacity                      0.15A @ 10ms              -
                                                                   1A cos φ 0.3              -
                                                  AC     125V - 250V 2A cos φ 0.7            -
                                                                   3A cos φ 1                -
                                     Minimum load                  100mA @ 24V               1mA @ 5V


                                    RTC: Connections
                                    More details are available in the website http://www.abb.com/abblibrary/DownloadCenter/, which also
                                    includes the entire circuit diagram 1SDM000091r0001.
                                    Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/,
                                    in particular for E1.2 in the kit sheet  1SDH000999r0604 and for E2.2-E4.2-E6.2 in the kit sheet
                                    1SDH001000r0604.