Page 261 - Sace Emax 2 Manual for design engineers
P. 261

Continued from the previous page                                   ABB | SACE Emax 2
                                     Faults                Possible causes             Suggestions
                                     It is not possible to remove
                                     the circuit-breaker from the   Fail Safe lock active  Discharge the closing springs of the
                                                                                       command
                                     disconnected position
                                                           Wrong threshold/time/curve selected Correct parameters
                                     Trip times different than   Thermal memory enabled  Disable it if it is not necessary
                                     expected              Zone selectivity enabled    Disable it if it is not necessary
                                                           Incorrect neutral selection  Modify the neutral selection
                                                                                       Correct operating condition with
                                     Rapid trip with I3 = Off  linst trip
                                                                                       short circuit at high current
                                                           Incorrect selection of the sensor  Set internal or external sensor
                                     High ground-fault current, but                    Correct operating condition (see use
                                     no trip occurs        Function G inhibited owing to high   cases in the chapter that describes
                                                           current
                                                                                       the protection)
                                                           No auxiliary supply or currents lower
                                     Display off and/or not backlit than minimum turn-on values  Correct operating condition.
                                                           Temperature outside range   Correct operating condition.
                                                           Current below the minimum   Correct operating condition.
                                                           threshold that can be displayed
                                                           Incorrect frequency setting  Set frequency
                                                           Harmonic distortion and/or crest
                                     Measurements incorrect or   factor off range      Correct operating condition.
                                     absent (current, voltage, etc)  Incorrect connection between   Check connections between
                                                           isolation transformer and   isolation transformer and
                                                           Measurement module          Measurement module
                                                           Rated voltage parameter setting
                                                           Error                       Set the correct parameters
                                     The expected trip does not                        Correct operating condition. Enable
                                     occur                 Trip excluded               trip if necessary
                                                           No auxiliary power supply and/or
                                     Opening data not displayed                        Correct operating condition.
                                                           battery low
                                                           The PIN has been disabled or has
                                     The PIN is not required  already been entered in the same   Operating condition correct; consult
                                                           programming session         chapter relating to the PIN
                                     Impossible to change any of   Trip unit in alarm condition  Correct operating condition.
                                     the parameters
                                                           Trip unit set remotely      Set it in local mode
                                     The language cannot be   The circuit-breaker is not open  Open the circuit-breaker
                                     changed               One of the possible power supplies  Power the trip unit with Vaux, Ekip
                                                           is not present              T&P or Ekip TT
                                                                                       Contact ABB or consult document
                                     PIN error             PIN wrong or lost
                                                                                       1SDH001501R0001
                                     Communication problems   Circuit-breaker in withdrawn   Insert modules, set circuit-breaker to
                                     with Ekip Com, Ekip Link or   position, Vaux absent or modules   Connected position, connect Vaux
                                     Ekip Signalling       not inserted properly
                                     State of CB Position field not                    Check for presence of Ekip Com
                                     aligned with circuit-breaker   Absence of Ekip Com or Ekip Link   or Ekip Link modules and connect
                                                           modules, or contact S75I
                                     position                                          contact S75/I


                                                                                                  Continued on the next page