Page 125 - SACE Tmax XT - Catalogue
P. 125

COMMUNICATION AND CONNECTIVITY                                                   4/29



          —

          Accessories for XT2-XT4 Ekip trip units













                           Ekip Com
                           The Ekip Com allows the MOE-E motor operator to be controlled, to determine the ON/OFF/TRIP state
                           of the circuit-breaker and to connect an electronic trip unit to a Modbus communication line. The Ekip
                           Com is available in two versions: one version for the circuit-breakers in the fixed/plug-in version and a
                           version complete with a connector for the fixed moving parts for circuit-breakers in the withdrawable
                           version.                                                                                    04
                           Main characteristics:
                           •  Installation: The Ekip Com module is inserted in the right-hand slot of the circuit-breaker and fixing is
                            carried out without any need for screws or tools. Connection to the trip unit is done by using a special
          —
          Ekip Com          small cable which is fitted with a cable guide. The connection towards the Modbus line is made by
                            means of the terminal box to which a 24V DC auxiliary power supply must also be connected, which
                            activates both the module and the protection trip unit.
                           •  Functions: The Ekip Com module can acquire the state of the circuit-breaker remotely and, in
                            combination with the MOE-E motor operator, allows the circuit-breaker to be opened and closed. If
                            combined with a trip unit fitted with a communication function (Ekip LSI or Ekip LSIG), the Ekip Com
                            module allows the trip unit to be connected to a Modbus network, offering the possibility of pro-
                            gramming the protections and acquiring the measurements and alarms when it is connected to a
                            control and/or supervision system. When it is connected to the HMI030 unit, it is possible to have this
                            data locally on the front of the switchboard.
   120   121   122   123   124   125   126   127   128   129   130