Page 150 - SACE Tmax XT - Catalogue
P. 150

7/4              SACE TMAX XT LOW VOLTAGE MOLDED CASE CIRCUIT-BREAKERS



          —

          Execution and installation













                           Conversion kits
                           The following conversion kits can be ordered for the different versions. This is applicable the whole Tmax
                           XT family, up to Tmax XT6.

                           •  Kit for converting a fixed circuit-breaker into the moving part of plug-in/withdrawable versions
                            The conversion kit converts a fixed circuit-breaker into a moving part of the plug-in/withdrawable
                            versions. When withdrawable versions are required, it is essential to order an accessory for the front of
                            the circuit-breaker to maintain the IP40 degree of protection along the entire insulation run. This ac-
                            cessory is made of the following options:
          —
          Conversion kit for     - front for the lever operating mechanism (FLD);
          converting a fixed     - motor operator (MOE);
          circuit-breaker into
          the moving part of a     - direct or transmitted rotary handle operating mechanisms (RHD or RHE).
          plug-in circuit-breaker    In the case where no accessory to be applied onto the front is indicated, the front for the lever oper-
                             ating mechanism (FLD) is automatically included in the order.

                           •  Kit for converting a fixed part of a plug-in version into the fixed part of withdrawable versions
                             The kit comprises:
                               - a guide for transforming the fixed part of the plug-in circuit-breaker into a fixed part of a with-
                              drawable circuit-breaker;
         —                     - a racking-out lever that allows the moving part to be inserted and withdrawn. The mechanism allows
         Conversion kit for
         converting a fixed   the circuit-breaker to be set to the disconnected position (with the power and auxiliary circuits dis-
         circuit-breaker into the   connected) with the compartment door closed, which is an advantage for operator safety. The ro-
         moving part of a with-
         drawable circuit-breaker  tary handle can only be inserted when the circuit-breaker is open. Once it has been removed or with-
                              drawn, the circuit-breaker can be set to the open/closed position;
                               - a flange for the compartment door, which replaces the one supplied with the fixed version of the
                              circuit-breaker.

                           •  Kit for converting a fixed circuit-breaker into the plug-in version for RC Sel residual current devices
                            for XT2-XT4-XT5
                            The RC Sel 4-pole residual current devices for the XT2, XT4 and XT5 can be converted from fixed ver-
                            sions to plug-in versions using the special kit.

                           •  Kit for converting plug-in circuit-breakers into withdrawable versions for RC Sel residual current
                            devices for the XT2-XT4-XT5
                            The RC Sel 4-pole residual current devices for the XT2, XT4 and XT5 can be converted from the plug-in
         —
         Conversion kit for   version to the withdrawable version using a special kit, which includes a component to apply to the
         converting a fixed   front of the residual current device so as to allow it to be withdrawn when the panel door is closed.
         part of plug-in version
         into the fixed part of a   This kit can also be assembled on fixed circuit-breakers equipped with a front for a lever operating
         withdrawable version
                            mechanism or the direct rotary handle, thus allowing the use of residual current devices.
                            In the plug-in to withdrawable conversion kit, there are also PIN connectors to be applied onto the
                            right side of the circuit-breaker to facilitate disconnection of the auxiliary circuits connected to the
                            residual current device.
                            For the XT1, XT2, XT3 and XT4, this kit also contains the opening solenoid of the residual current de-
                            vice dedicated to the withdrawable version, which is fitted with a connector for the fixed part and the
                            moving part.
   145   146   147   148   149   150   151   152   153   154   155