Page 152 - SACE Tmax XT - Catalogue
P. 152

7/6              SACE TMAX XT LOW VOLTAGE MOLDED CASE CIRCUIT-BREAKERS



          —

          Execution and installation













                           Connectors for electrical accessories
                           Plug-in circuit-breaker
                           In the plug-in version of the SACE Tmax XT circuit-breakers, the auxiliary circuits can be disconnected by
                           means of two different types of adapter:
                           •  a plug and socket to be fixed on the bottom of the panel: for the XT1, XT2, XT3, XT4 and XT5;
                           •  a plug and socket installed on the rear of the circuit-breaker and in the fixed part of the plug-in devices:
                            for the XT2, XT4 and XT5.

                           Plug and socket on the back of the panel
                           To make it easier to connect/disconnect the auxiliary circuits, wired electrical accessories can be con-
                           nected to one or more plug and socket connectors on the back of the panel.
                           3, 6, 9 and 15 PIN connectors are available. The cables connect/disconnect the auxiliary circuits in a fast
                           and simple way without the aid of any dedicated tools.
                           Consider the number of cables of each electrical accessory when calculating the number of connectors
         —                 required.
         Plug and socket adapters
         on the back of the panel
                           Number of cables XT1-XT2-XT3-XT4 accessories  XT5-XT6 accessories
                                        SOR, UVR / External Neutral Ekip Dip trip
                           2            units / PTC for Ekip M-LRIU / Ekip Com   YO, YU / Ekip Com Modbus RTU /
                                        Modbus RTU / Ekip Com Modbus TCP STA  Ekip Com Modbus TCP STA
                           3            RC SA / 1 AUX                  1 AUX
                                        24V DC/Internal bus cable /    24V DC/Internal bus cable / Ekip Signaling 1K / Ekip Com
                           4
                                        Ekip Com Modbus RTU STA / AUE  Modbus RTU STA / Ekip Maintenance Module / AUE
                           5            MOE-E / Selectivity cable      Selectivity cable
                           6            Ekip Com  / Residual current device  Residual current device, MOE-E
                                               (1)
                           7            MOE (with AUX-MO) / MOD (with AUX-MO)  -
                           8            -                              MOE (with AUX-MO)
                           (1) Ekip Com for Ekip LSI, LSIG and M-LRIU

                           Plug and socket adapters on the rear of the circuit-breaker and inside the fixed part
                           For the plug-in versions of the XT2, XT4 and XT5 circuit-breakers, the auxiliary circuits can be automati-
                           cally disconnected by means of an adapter installed on the rear of the circuit-breaker and inside the
                           fixed part of plug-in versions.
                           The 12 PIN connector can be used only with accessories functioning at a voltage lower than 250V AC/DC.
                           The cables connect/disconnect the auxiliary circuits in a fast and simple way without the aid of any
         —                 dedicated tools. Wiring is to be carried out by the Customer.
         Plug and socket adapter
         placed on the back
         of the moving part  Circuit-breaker  Number of plugs and sockets installed on the rear of the circuit-breaker and inside the fixed part
                           XT2-XT4      1
                           XT5          2






         —
         Plug and socket adapter
         in the fixed part
   147   148   149   150   151   152   153   154   155   156   157