7/40 SACE TMAX XT LOW VOLTAGE MOLDED CASE CIRCUIT-BREAKERS
—
Remote control
Operating mode: Manual Operating mode: Auto
I: ON discharged springs I: ON discharged springs
OFF
SOR / UVR / SA release push- SOR / UVR / SA release
tripping / TU button tripping / TU OFF
on the ON push- ON push-
motor pushbut- button
O: OFF discharged springs O: OFF discharged springs button
ton on the from
recharge motor OFF push-button from remote
the springs from remote remote
O: OFF charged springs O: OFF charged springs
Stored energy motor operators - MOE and MOE-E XT5 and MOE XT6
Signaling of the springs status: LED power-ON
charged springs/discharged
springs Signaling of the circuit-breaker
status ON-OFF
Lever to recharge the springs
— Opening push-button
Stored energy motor
operator (MOE)
AUTO-MANUAL-LOCKED selector Sliding cover for AUTO mode
Closing push-button
Position for the optional locks
Slot for padlock device
The MOE or MOE-E stored energy motor operator available for the XT5 and XT6 is supplied:
• with 1m long cables;
• with connectors for the fixed part and moving part of withdrawable devices. If the motor operator is
used with fixed or plug-in circuit-breakers, the connector can be easily removed;
• with a flange, to use instead of the standard one supplied with the circuit-breaker;
• with a padlock device, only removable when the motor is in the open position. The padlock device ac-
cepts up to three 8mm padlocks;
• with a lock for the AUTO-MANUAL selector;
• with auxiliary contacts that allow the motor control mode (manual or remote) signal to be routed out-
side;
• (on request) the motor operator can be equipped with a key lock (see the Chapter "Accessories" - sec-
tion "Locks");
• (on request) the motor operator can be equipped with a key lock to safeguard against manual operation
(MOL-M) (see the Chapter "Accessories" - section "Locks").